Gree GMV6 HR DC Inverter VRF Units Service Manual
33
Master unit setting (SA8):
Master and Slave
Unit Setting
DIP Switch (Two Digits)
Position
1
2
Master unit
ON
OFF
Slave unit
OFF
OFF
Step 4:
Power on the indoor and outdoor units.
Power on all indoor and outdoor units. In this case, all modules of the outdoor unit indicate that the
unit is in "Not commissioning" status.
L E D 3
Step 5:
Set the static pressure for the outdoor unit.
When the indoor and outdoor units are powered on, and the unit is to be commissioned, set the
static pressure mode for the unit according to the design requirements for the outdoor static pressure of
the project. Five static pressure modes are available: The factory default static pressure mode 0
represents 0 Pa outdoor static pressure, mode 1 represents 30 Pa, mode 2 represents 50 Pa, mode 3
represents 80 Pa, and mode 4 represents 110 Pa.
Each basic module can be set separately or uniformly by the master module. When basic modules
are set separately, the static pressure value of each module can be different; when the modules are set
uniformly, the static pressure value of each module remains the same. When a static pressure value is
set in either of the two modes, the previous mode setting limit is automatically released. The static
pressure value of each basic module is subject to the last received set value. The setting procedure is as
follows:
When the unit is to be commissioned, press and hold the SW1 up button on the master unit for over
5 seconds. The system enters the function setting status. The master unit displays "A7 (blinking) 00
(blinking) 00 (blinking)" by default, and other modules display current statuses.
Then, press the SW1 up button and the SW2 down button on the master unit to select the
corresponding function/parameter till "A7 (blinking) 00 (blinking) 00 (blinking)" is displayed, indicating
outdoor static pressure setting. Press the SW3 confirm button to enter the function setting. The master
unit displays as follows, and other basic modules display in normal working mode:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
1G
On
01
Blinks
OC
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding basic module: 00
means all modules, 01~04 means module 1 to module 4.
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...