Gree GMV6 HR DC Inverter VRF Units Service Manual
67
On the master unit, press and hold the SW2 down button for over 5 seconds. The master unit
displays the current function setting status, and other modules display based on their current status.
Press the SW1 up button and the SW2 down button on the master unit to select the corresponding query.
The default selection is A6.
In function query status, if there are two levels of menus, you can press the SW4 back button to
return to the previous level. Press the SW4 query button again to exit query status.
In function query status, if you do not press any button on the master unit in 5 minutes, the system
will automatically exit the current screen and the unit will resume displaying the current status.
4.1.2.4.1 n6 Fault Query
Press the SW1 up button and the SW2 down button to select fault query. The master unit displays
as follows:
LED1
LED2
LED3
Function Code
Display status
Current
process/mode
Display status
Current status
Display status
n6
Blinks
00
Blinks
00
Blinks
Press the SW3 confirm button on the master unit to confirm the selection.
Introduction:
This function is used to query historical faults in the system. Up to five historical faults can be stored
in the order of time.
Operations:
In fault query status, press the SW1 up button and the SW2 down button. LED3 circularly displays
the code and address of the faulty module in history in the order of time (at an interval of 1s), and LED2
displays the fault sequence number. If there is no historical fault, LED2 and LED3 display "00" by default.
Up to five latest historical faults can be queried. Faults that can be stored and queried are as follows:
1
High pressure protection
20
Inverter compressor over-current protection
2
Low pressure protection
21
Current detection circuit fault of the inverter
compressor driver
3
Lack-of-refrigerant protection
22
Loss of synchronization protection for the inverter
compressor
4
Air discharge low temperature protection
23
Communication fault between the primary
controller and inverter compressor driver
5
Over low pressure ratio protection
24
Over temperature protection for the inverter
compressor driver module.
6
Over high pressure ratio protection
25
Temperature sensor fault of the inverter
compressor driver module.
7
Four-way valve air backflow protection
26
Charging loop fault of the inverter compressor
driver.
8
High pressure low protection
27
Under voltage protection for DC bus of the
inverter outdoor fan driver
9
High temperature protection for compressor 1
28
Over voltage protection for DC bus of the inverter
outdoor fan driver
10
High temperature protection for compressor 2
29
IPM module protection for the inverter outdoor
fan driver.
11
Compressor 2 over-current protection
30
Inverter outdoor fan startup failure.
12
Shell roof high temperature protection for
compressor 1
31
Inverter outdoor fan phase loss protection.
13
Shell roof high temperature protection for
compressor 2
32
Inverter outdoor fan driver module reset.
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...