Gree GMV6 HR DC Inverter VRF Units Service Manual
44
4 Unit Function Settings
4.1 Outdoor Unit
4.1.1 DIP Switch Settings
Capacity DIP switch
Centralized controller
Master/
Slave unit
Code
Name
Meaning
Default Setting
Remarks
SA1_capacity
Capacity DIP
switch
Defines the rated
capacity of the unit.
Depending on
the model
The DIP switch is set by the
factory and cannot be changed.
SA2_Addr-CC
Address DIP
switch for
centralized
control
Defines and
distinguishes addresses
of different systems for
centralized control of
multiple systems.
00000
The code is used only for
centralized control. Otherwise,
keep the default setting. This
address can be set only on the
master unit.
SA8_MASTER-S
Master
module
setting DIP
switch
Defines the master
module.
00
Exactly one module must be
configured as the master
module in a refrigerating
system. The master module
status is set by default.
NOTES!
①
The function DIP switches must be set when the outdoor unit is powered off. A DIP switch setting
takes effect after the unit is re-powered on.
②
The master module SA8 DIP switch must be reset in the project. SA1 DIP switch cannot be
changed. The default settings of other DIP switches do not need to be changed if there are no
special requirements.
4.1.1.1 Unit Capacity DIP Switch (SA1_capacity)
This DIP switch is set by the factory before shipment, and cannot be changed. Otherwise, the
system will work abnormally and even damage the compressor.
4.1.1.2 Address DIP Switch for Centralized Control (SA2_Addr-CC)
This DIP switch indicates the address for centralized control of different refrigerating systems. It is
set to 0000× by default.
If centralized control is not required between multiple refrigerating systems, keep the default setting
of this DIP switch.
If centralized control is required between multiple refrigerating systems, set as follows:
(1) Be sure to set the DIP switch on the master unit.
(2) Setting this DIP switch on non-master units in a refrigerating system is invalid and unnecessary.
(3) Be sure to set the address DIP switch for centralized control (SA2_Addr-CC) on the master unit of a
refrigerating system to "0000x". Then, this system is the main system.
(4) Set the address DIP switch for centralized control (SA2_Addr-CC) on the master units of other
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...