Gree GMV6 HR DC Inverter VRF Units Service Manual
204
2.156 "P7" Abnormal Temperature Sensor of Compressor Drive
Board
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P7, it
indicates the abnormal temperature sensor of compressor drive board.
Possible causes:
■ The com
pressor drive board operates improperly.
Troubleshooting:
"P7" Abn ormal
Temperature Sen sor of
Compressor Drive Boar d
Is th e p roblem so lve d after
the unit is powered off and powere d o n for
more th an thr ee times?
The co mpr essor drive boar d
ope rate s imprope rly
No
Replace th e compre ssor drive
boa rd
Yes
2.157 "P8" IPM Over Temperature Protection for Compressor Drive
Board
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P8, it
indicates the IPM over temperature protection for the compressor drive.
Possible causes:
■ The IPM module's screws are not tightened;
■ The IPM module is not covered, or unevenly covered by thermal grease, or covered by dried
thermal grease;
■ The compressor drive board operates improperly.
Troubleshooting:
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...