Gree GMV6 HR DC Inverter VRF Units Service Manual
29
—
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
05_ detect internal
communication
db
ON
05
ON
C2
ON
The system has detected
“communication
malfunction between main
control and inverter
compressor driver”.
db
ON
05
ON
C3
ON
The system has detected
“communication
malfunction between main
control and inverter fan
driver”.
db
ON
05
ON
CH
ON
Indoor/outdoor units’ rated
capacity ratio is too high.
db
ON
05
ON
CL
ON
Indoor/outdoor units’ rated
capacity ratio is too low.
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 9:
The unit debugging step 06 is “outdoor unit’s parts inspection”.
If there is no abnormality in the detection, the display is below, and then it automatically enters the
next step of detection.
—
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code Display status
06_outdoor unit’s
parts inspection
db
ON
06
ON
OC
ON
The system detected that
there’s no fault for outdoor
unit’s parts. Then it will
automatically enter into
the next step.
If an abnormality is detected, it will stay in the current state and manual troubleshooting is required.
The corresponding faults are as below:
—
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
06_
outdoor unit's
internal
components
confirmation
db
ON
06
ON
Corresponding
error code
ON
The system detected that
there’s fault for outdoor
unit’s parts.
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 10:
The unit debugging step 07 is “indoor unit’s parts inspection”.
If there is no abnormality in the detection, the display is as below, and then it automatically enters
the next step of detection.
—
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
07_ indoor unit
componets
inspection
db
ON
07
ON
OC
ON
The system detected
that there’s no fault for
indoor unit’s parts. Then
it will automatically enter
into the next step.
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...