Gree GMV6 HR DC Inverter VRF Units Service Manual
126
Yes
"d7" Humidity Sen sor Fault
Remove the foreign
matters and plug it tightly
The detection circuit may
ope rate impro perly
Yes
Replace th e main control
boa rd
No
Is th e p roblem so lve d after the
humidity sensor is re placed?
Whether th e i nter face
terminal between the main boa rd
and hu mid ity sen sor gets lo ose or
contains forei gn matters?
No
2.57 "d8" Water Temperature Sensor Fault (Reserved)
2.58 "d9" Jumper Cap Fault
Fault display:
wired controller of indoor unit and receiver of indoor unit display
Fault diagnosis:
A fault is reported if the jumper cap does not match the main board.
Possible causes:
■ The jumper cap is not installed;
■ The jumper cap is numbered inc
orrectly;
■ Abnormal detection circuit.
Troubleshooting:
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...