2.151 "P1" Malfunctioning Compressor Drive Board
Fault display: wired controller of indoor unit displays
Fault diagnosis:
If the fault code displayed on the wired controller of the indoor unit is P1, check the fault code
displayed on the 2-digit digital LED of the main control board of the outdoor unit, based on which you are
able to identify the specific fault of the compressor drive board. Then, troubleshoot the fault according to
the corresponding troubleshooting methods.
Possible causes:
■ Inverter compressor over
-current protection (2-digit digital LED of the main control board of the
outdoor unit displays P5);
■ IPM module protection for the compressor drive (2
-digit digital LED of the main control board of
the outdoor unit displays P6);
■ Communication fault of compressor drive (2
-digit digital LED of the main control board of the
outdoor unit displays C2).
Troubleshooting:
based on the faults displayed on the main board of the outdoor unit.
2.152 "P2" Input Voltage Protection for the Compressor Drive Board
Fault display:
wired controller of indoor unit displays
Fault diagnosis:
If fault code displayed on the wired controller of the indoor unit is P2, check the fault code displayed
on the 2-digit digital LED of the main control board of the outdoor unit, based on which you are able to
identify the specific fault of the compressor drive board. Then, troubleshoot the fault according to the
corresponding troubleshooting methods.
Possible causes:
■ Over voltage protection for the DC bus of compressor drive (2
-digit digital LED of the main control
board of the outdoor unit displays PH);
■ Under voltage protection for the DC bus of compressor drive (2
-digit digital LED of the main
control board of the outdoor unit displays PL).
Troubleshooting:
based on the faults displayed on the main board of the outdoor unit.
2.153 "P3" Reset Protection for the Compressor Drive Module
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P3, it
indicates the reset protection for the compressor drive board.
Possible causes:
■ The compressor drive operates improperly
Troubleshooting:
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...