Gree GMV6 HR DC Inverter VRF Units Service Manual
180
2.117 "J9" Low Pressure Ratio Protection
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
When the ratio between the system high pressure and the low pressure during operation detected
by the pressure sensor is smaller than 1.8, the unit will stop running to ensure safe operation.
Possible causes:
■ The pressure sensor is abnormal;
■ The ambient temperature where the unit operates exceeds the limit.
Troubleshooting:
"J9" Over Low Pressu re
Ratio P rote ction
Replace th e p ressur e
sensor
Yes
Whether the air return
te mperature of the unit excee ds the limit during
operation (requirements in cooling mode: outdoor ambient
te mperature -5°C to +50°C, indoor ambient temp erature 16°C to 32°C;
requirements in heating mode: outdoor ambient temperature
-20°C to +24°C, indoor ambient
te mperature 16°C to 30°C)?
Whether th e h igh and low
pressure sensors are op erating prope rly
(based on the Tab le of Characteristics
of P ressur e S ensors)?
No
This case is normal as i t is
subject to ambient
temperature
Yes
2.118 "L0" Indoor Unit Fault (Unified)
Fault display:
wired controller of indoor unit displays
Applicable models:
all indoor units
Possible causes:
■ The indoor unit is faulty.
Troubleshooting:
When multiple indoor units are installed in the same place, you can use the function of "indoor unit
engineering SN query and fault indoor unit identification" to fast locate the faulty indoor unit or the
corresponding indoor unit controlled by a wired controller. The detailed operations are as follows:
"C01" indoor unit engineering SN and fault query:
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...