Gree GMV6 HR DC Inverter VRF Units Service Manual
51
Basic module refrigerant recycle:
Step 3:
Set the basic module that needs refrigerant recycle to emergency status, close the liquid
pipe stop valve of the module in emergency status, and then select 02 in step 2 to enter refrigerant
recycle of the basic module, as shown below:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
A2
On
02
On
Module high
pressure
On
LED3 displays the high pressure value of the module.
Step 4:
When the high pressure value displayed by LED3 continuously blinks (if the high pressure is
below 0, 0 is displayed), quickly close the air pipe stop valve of the emergency module, and press SW3
on the master unit to confirm refrigerant recycle. The entire system will stop immediately. If the high
pressure value displayed by LED3 continuously blinks and you do not operate in 3 minutes, the system
forcibly stops.
Press the SW4 back button on the master module to return to the previous process or exit the
function setting status.
Note:
Before the refrigerant recycle of a basic module, the liquid pipe stop valve of the basic module must
be closed. After refrigerant recycle, the system cannot be restarted within 10 minutes.
4.1.2.3.2 "A6" Cooling/Heating of the Entire System
Introduction:
This function sets the cooling/heating mode of the entire system. Available modes include:
Outdoor Unit Function Mode
Available Indoor Unit Operation Modes
Code
Name
nA
Cooling and
heating
Cooling, dry, heating, and fan
(Note: Heating mode cannot run with other modes at the same time.) (Default setting)
nC
Cooling only
Cooling, dry, and fan
nH
Heating only
Heating and fan
(Note: Heating mode cannot run with other modes at the same time.)
nF
Fan
Fan
The user or administrator needs to set the mode of the outdoor unit based on the actual usage to
avoid conflicts.
Setting steps:
Step 1:
Enter A6 cooling/heating setting of the entire system, and ensure that the master module
displays as follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
A6
On
nC
Blinks
nC
Blinks
Step 2:
Press the SW1 up button and the SW2 down button to select the corresponding
cooling/heating mode.
Содержание GMVVQ1015WM/C-X
Страница 418: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 416 GMV VQ400WM C X GMV VQ450WM C X...
Страница 419: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 417 GMV VQ504WM C X GMV VQ560WM C X GMV VQ615WM C X...
Страница 420: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 418 NCHS1D...
Страница 421: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 419 NCHS2D...
Страница 422: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 420 NCHS4D...
Страница 423: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 421 NCHS8D...
Страница 426: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 424 6 1 2 Heating Operation...
Страница 427: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 425 6 1 3 Main body Cooling...
Страница 428: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 426 6 1 4 Main body Heating...
Страница 430: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 428 6 2 2 Heating Operation...
Страница 431: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 429 6 2 3 Main body Cooling...
Страница 432: ...Gree GMV6 HR DC Inverter VRF Units Service Manual 430 6 2 4 Main body Heating...
Страница 433: ...JF00304244...