GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
65
1.3 Procedure of Insulation
a. Select insulation materials based on design requirements.
b. Wear the insulation sleeve before connecting refrigerant pipes. Users cannot cut the insulation
material apart and then wrap up with ties after connecting the pipes by welding.
c. Specifications of the insulation sleeve must match with that of the refrigerant pipes.
d. Reserve a distance of about 200 mm near the welding point to protect the insulation sleeve during
welding. After performing the air-tightness test, perform insulation to the welding point separately to
ensure continuity of the insulation sleeve.
e. The insulation layer cannot crack during construction. Bond the insulation material joints with special
glue and then wrap them with electrical adhesive tape. The width of the adhesive tape must be 50 mm or
more to ensure secure connection.
f. Use glue to bond the insulation material at the water outlet to the unit to prevent dewing.
g. Wrap joints of indoor/outdoor units with insulation materials. There must be no gap between the joint
and the wall of the indoor/outdoor unit, as shown in the following figure.
No gap
2. Insulation for the Condensate Water Pipe System
2.1 Insulation Materials
Use closed-cell foam insulation materials with retardant grade of B1.
The heat conductivity is not greater than 0.035 w/(m·k) when the average temperature is 0
°C
.
2.2 Thickness of the Insulation Layer
Thickness of the insulation layer for the condensate water pipe must be greater than 10 mm.
2.3 Bond the insulation material joints with special glue and then wrap them with plastic adhesive. The
width of the adhesive must be greater than 5 cm to prevent dewing.
2.4 Insulation is not required for the outdoor part of condensate water pipes.
3. Insulation for Air Ducts
3.1 Insulation for air duct components and devices must be performed after the air leakage test is
performed or after quality check.
3.2 Use centrifugal glass wool or rubber and plastic materials for insulation or use novel insulation air
ducts.
3.4 The insulation layer should be flat and tight without any crack or gap.
3.5 Thickness of the Insulation Layer
For the air supply and return air pipe laid in a room without an air conditioner, thickness of the rubber and
plastic insulation layer is 35 mm.
For the air supply and return air pipe laid in an air conditioning room, thickness of the rubber and plastic
insulation layer is 20 mm.
3.6 Supports, hangers, and brackets of the air duct must be installed outside the insulation layer. A chock
must be provided between the support, hanger, or brackets and the air duct.
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...