GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
173
is faulty. Check communication lines connecting the ODU and IDUs.
Note: After AP1 is replaced, you should power on the ODU and IDUs at the same time or power on the
ODU first; otherwise, ―CC does not have module‖ will be prompted and a ―C0 fault‖ alarm will be reported
by the IDUs.
③
Master ODU engineering debug setting
Debug the entire system after master module AP1 replacement.
④
System parameter setting
After system debug, reset system parameters.
For details, refer to section 1 ―ODU Function Setting‖, in
part II, chapter III.
1.3 Cautions on Replacement of Slave ODU AP1
Before replacing slave module AP1, set DIP identical to that of the faulty AP1, check wiring, and then
power on the AP1.
2. Cautions on IDU AP1 Replacement
Before replacing IDU AP1, determine the module is a master IDU or a slave IDU.
2.1 AP1 DIP Setting and Jumper Cap Confirmation
Whatever the AP1 you replace is a master IDU AP1 or a slave IDU AP1, after it is replaced,
check original DIP setting and model.
Configure capacity DIP for the new AP1 and confirm its jumper cap, fan overload detect
terminal, and overflow detect terminal. They should be kept identical to those of the faulty
AP1.
Their positions and corresponding silkscreen are as follows:
Capacity DIP: S1 (Capacity)
Jumper cap: U22 (Jump)
Overflow detect terminal: CN35(WATER-DTCT)
Fan overload detect terminal: CN36(OVC-FAN)
2.2. Restoring AP1 Engineering Parameters to Factory Settings (This Step Is Not
Required for Original Packaged Parts)
After wiring, whatever the AP1 is a master IDU AP1 or a slave IDU AP1, the new AP1 must
be restored to factory settings. There are three methods to restore engineering parameter
settings:
①
If the IDU is configured with wired control, set P35 and P36 to default values.
②
If the IDU is configured with wireless control, use the special control YV1L1 to set P35
and P36 to default values.
③
If the IDU is configured with wireless control and special control, you can restore
engineering settings through the AP1 SW1 button. After AP1 is powered on, press and
hold SW1 for 5 seconds. If a tick sound is heard, release the button.
U22
CN3
5
CN3
6
S1
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...