GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
18
VII. Precautions on Refrigerant Leakage
Personnel related to air conditioning engineering design and installation operators must abide by
the safety requirement for preventing refrigerant leakage specified in local laws and regulations. If such
safety requirement is unavailable in local documents, the design and operation must be implemented
based on the following principles: GMV5 series VRF units adopt the R410A refrigerant, which is
nonflammable and nontoxic. However, the space for refrigerant leakage must be sufficient to ensure that
the refrigerant concentration does not exceed that specified in the safety requirement; otherwise, people
involved can be stifled by the refrigerant.
The maximum refrigerant charge and maximum refrigerant concentration in the system are
calculated directly based on the size of the air conditioning space. The unit of refrigerant concentration is
1 kg/m³.
1) Flow direction of refrigerant leakage.
2) Room for refrigerant leakage. Since the concentration of refrigerant is greater than that of air, pay
attention to the spaces where the refrigerant may residue, for example, the basement.
Method for calculating the maximum concentration of refrigerant:
(1) Calculate the refrigerant charge quantity of each system.
Charge quantity of an ODU upon delivery (for the system consisting of multiple modules in parallel,
the accumulative charge quantity of modules upon delivery is used) + Onsite charge quantity = Total
refrigerant charge quantity in the system (kg)
(2) Calculate the volume of maximum air conditioning space (m³).
Volume of air conditioning space (m³) = Len gth x Width x Height
Note: The length, width and height here refer to the effective length, width and height of the indoor
space.
(3) Calculate the maximum refrigerant concentration of the refrigeration system.
Total refrigerant quantity of the system
------------------
≤ Maximum supported concentration (kg/m³)
Minimum volume of air conditioning space
Note: If the maximum supported refrigerant concentration is not available in relevant local standard,
use 0.3kg /m³ as the maximum supported refrigerant con centration.
(4) If the maximum refrigerant concentration exceeds the allowed threshold, the refrigeration system
must be redesigned. In this case, separate the refrigeration system into multiple small-capacity
refrigeration systems, or contact local Gree sales company.
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...