GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
129
Part 2 Exception and Troubleshooting
Exception Analyzing and Troubleshooting
(1) Form analyzing
1. Control
Fault
code
Fault
Possible reasons
Solution
F0
Faults in the ODU's
main board (such as
memory and
address chip
exceptions)
1. The clock chip on the main board
is damaged.
2. The memory chip on the main
board is damaged.
3. The address chip on the main
board is damaged.
1. Replace the small CPU board.
2. Replace the control board.
3. Replace the control board.
FC
Faults in the
constant frequency
compressor's
current sensor
1. The constant-frequency
compressor is not started.
2. The current detection board is
faulty.
3. The main board's detection
circuit is faulty.
1. If the compressor is not started, check if the AC
contact is closed. If not, replace the AC contact.
If the connection is loose, reconnect it;
2. Replace the current detection board.
3. Replace the main board.
U2
Wrong outdoor
capacity code
setting
1. The capacity code is wrong.
2. The dial component is faulty.
1. Modify the capacity code setting.
2. Replace the main board.
U3
Power phase
sequence protection
1. The three-phase power cable is
not connected correctly.
2. The main board's detection
circuit is faulty.
1. Check connection of the power cable.
2. Replace the control board.
UL
Wrong emergency
operation dial code
1. The dial setting is wrong.
2. The dial component is faulty.
1. Modify the dial setting.
2. Replace the main board.
C0
Communication
failure between
indoor and ODUs
and IDU's
communicator
1. The communication cable is not
connected.
2. The communicator is
disconnected.
3. The communication cable is
poorly connected.
4. The communicator controller is
faulty.
If C0 is not displayed on the control board of the
ODU, check the network between the IDU and
communicator. If C0 is displayed, check the network
between the IDUs and ODUs and between the IDU
and communicator as follows:
1) Check if the cables connecting the control board of
the ODU and the IDU and connecting the IDU and
communicator are loose. If yes, reconnect them;
2) Check if the cables connecting the control board
and IDU and connecting the IDU and
communicator are broken. If yes, replace the
cables;
3) Check the contact of the communication cables;
4) Replace the control board. If the fault is solved, the
control board is faulty. Replace the IDU. If the fault
is solved, the IDU is faulty.
C2
Communication
failure between
main control board
and inverter
compressor drive
1. The communication cable is not
connected.
2. The communicator is
disconnected.
3. The communication cable is
poorly connected.
4. The communicator is faulty.
1) Check if the cable connecting the control board
and the compressor's drive board is loose. If yes,
reconnect it;
2) Check if the cable connecting the control board
and compressor's drive board is broken. If yes,
replace the cable;
3) Check the contact of the communication cable
connecting the control board and compressor's
drive board;
4) Replace the control board. If the fault is solved, the
control board is faulty. Replace the compressor's
drive board. If the fault is solved, the compressor's
drive board is faulty.
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...