GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
318
8. Troubleshooting
8.1 Hardware Faults
Table 6. Hardware faults
Symptom
Possible Cause
Troubleshooting
A software communication
fault alarm is reported, and
some or all units' running
state is not displayed or
cannot be controlled.
The communications lines
are not twisted pairs.
Replace the communication
lines with twisted pairs.
Gateway damages.
Replace the damaged
gateway.
Communication lines
interrupt.
Weld the interrupted lines.
Communication lines are
short circuited.
Repair the short circuited
part.
Twisted pairs are too close
to the power lines (less than
15 cm clearance), resulting
in disturbance that affects
communication.
Separate the two types of
lines. If their clearance is
less than 15 cm, cover them
with sheath separately.
Communication interface
connection error
Refer to related instructions
to connect the
communication interfaces.
Though lines are normal,
a software communication
fault occurs and some or
all units' information is not
displayed.
ODUs, after being replaced
with chips or reset with DIP,
are not re-powered on.
Re-power on the ODUs.
The serial port configured
by the software is
inconsistent with that
connected to PCs.
Connect the PCs to the
serial port configured by the
software or change the serial
port setting in the software.
Units are not powered on.
Power on the units.
ODUs or IDUs are not
equipped with chips, or
chips are inversely installed.
Install the chips in a correct
direction and power on the
units.
Unit address is incorrect or
replicate.
Correct the incorrect
address settings.
Though lines and devices
are normal, information of
devices of a floor is not
displayed.
Maybe a repeater is
required. If such a device
has been installed, maybe
wiring is incorrect.
Reinstall the repeater in a
correct manner.
A communication fault alarm
is reported, all units' running
state is not displayed,
and the TX LED on the
converter is steadily on.
Polarities of communication
lines are not distinguished
or they are connected in a
wrong order.
Check communication lines
for their polarities and
connect them in a correct
order.
Lines, devices, and setups
are all normal. However, a
software communication
fault alarm is reported.
The display or controller
does not match units.
Check the models of the
controller and operation
panel. If they do not match
unit specification, replace
them.
8.2 Software Faults
8.2.1 Software Abnormalities
1. Though the username and password ent
ered are correct, the system prompts ―Please contact the
administrator‖, as shown in the following figure:
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...