GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
322
Possible cause:
Communication between the server and gateway fails.
Solution:
(1) Check whether a hardware fault exists. Check gateway running. For details, refer to section 7.1
"Hardware Faults".
(2) If there is not hardware fault or the fault is addressed, restart BAS Service. There are two methods to
restart BAS Service.
Method a
①
Right click the BAS Manager icon in the status bar at the lower right corner on the desktop and choose
―Open‖.
②
In the displayed ―BAS Manager‖ window, click ―Start‖ to enable BAS Manager.
Method b
Choose ―Start‖
-
> ―All Programs‖
-
> ―Gree CAC Remote Monitoring System‖
-
> ―ServiceManager‖. In the
displayed ―BAS Manager‖ window, click ―Start‖ to enable BAS Manager.
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...