GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
277
as location.
Each Modbus gateway should be supplied with power independently. Therefore, you should install
as many 220V AC power sockets as possible in the control cabinet. It is not allowed to connect
multiple Modbus gateways to a same power socket.
Make sure to keep at least 15 cm between communication lines and strong current lines. It is
forbidden to bind them together. If their distance is less than 15 cm, put them into shield tubes
respectively to prevent electromagnetic disturbance.
The control cabinet must be installed indoors. Avoid knock or exposure to sunshine or rain. It should
be locked as well to avoid body contact.
1.4.2.3 Communication System Installation
The Modbus gateway works to get through the communication
(1) Between the Modbus gateway and the Gree Web-based Remote Monitoring and Control
System/BMS.
(2) Between the Modbus gateway and the air conditioning system.
1. Selection of Communication Lines
(1) Communication lines between the Modbus gateway and the Gree Web-based Remote Monitoring
and Control System/BMS
Type
Size
Applicable Standard
Remarks
Category five
twisted pairs
24AWG
(2
0.6 mm)
TIA/EIA-568-A
An optoelectronic repeater is required
when the communication distance is
more than 800 m.
(2) Communication lines between the Modbus gateway and the air conditioning system
Type
Length
(m)
Wire
Gauge
(mm
2
)
Applicable
Standard
Remarks
Light/Ordinary
polyvinyl
chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L
500
2
0.75
IEC
60227-5:2007
1. If the wire diameter is enlarged to 2 × 1
mm
2
, the total communication line
length can reach 800 m.
2. The cord shall be Circular cord (the
cores shall be twisted together).
3.If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.
Note: The length of the CAN2 bus connecting the Modbus gateway with master ODUs should not
exceed 500 m, as shown in the following figure:
ODU system 2
Master ODU
ODU system n
Master ODU
ODU system 1
Master ODU
……
Modbus gateway
Max.: 500 m
CAN2 bus
―n‖ (n≤16) represents the quantity of the air conditioning systems.
2. Connection of Communication Lines
Precaution
Only serial connection is allowed for all communication lines of the Modbus gateway. The star
connection is prohibited.
(1) Communication lines between the Modbus gateway and the Gree Web-based remote monitoring and
control system/BMS
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...