GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
104
10 Is the total length of pipes less than 1000 m?
11
Is the spacing between the ODU and the first disperse pipe larger than 90 m? If
yes, is the corresponding pipe diameter increased?
12
Is the spacing between the IDU and the nearest disperse pipe larger than 10 m?
If yes, is the corresponding pipe diameter increased?
13 Does the wall thickness of copper tubes meet design requirements?
14 Are disperse pipes horizontal or vertical?
15
Does the diameter of cables connected with IDUs and ODUs comply with unit
design requirements?
16 Do the circuit breaker and leakage switch comply with unit design requirements?
17 Is the spacing between the power cable and the TV set larger than 1 m?
18 Do communication cable materials comply with unit design requirements?
19 Are all communication cables of IDUs and ODUs serially connected?
20
Is the last-communicating IDU installed with a communication-matched
resistance?
21 What is the load of the selected IDU model?
22
Is the foundation of ODU firm? Do shock absorption and water drainage comply
with requirements?
23 Are basic modules installed on the same horizontal line?
24 Does the drainage pipe of IDU retain a 1/100 ratio of slope?
25 Is the raised height of drainage pipe of IDU less than 85 cm?
26 Is the drainage of IDU smooth?
27 Does a U-shaped trap exist in the drainage pipe of IDU?
28
Are the air outlet and air return vent of IDU connected with soft connectors? Is a
plenum chamber installed for air return?
29 Is the water pipe of IDU installed with an air exhaust vent?
30 Is "MASTER" stuck to the wired controller or panel of the master IDU?
31 Does appending refrigerants to the system comply with requirements?
32 Does the ODU run with static pressure? Has a static pressure value been set?
33 Has the ODU been preheated for more than eight hours before commissioning?
Step 3: Commissioning Operation
3.1 Precautions
1) Before starting commissioning, make sure that the unit compressor has been preheated for more than
eight hours and check whether preheating is normal by touching. Commissioning can be started only
when preheating is normal. Otherwise, the compressor may be damaged. Commissioning must be
performed or guided by professional personnel.
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...