GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
97
32
Inlet-tube temperature of condenser
°C
This parameter is invalid for the
GMV5 series.
Note:
If a p
arameter value is negative, LED3 circularly displays the negative code "nE‖ and the numeric value
every one second. For example, for -30
C, LED3 alternately displays ―nE‖ for one second and then ―30‖
for another second.
The discharge temperature and environment temperature are displayed as four-digit values, circularly
displaying the higher two digits and the lower two digits. For example, if "01" and "15" are alternately
displayed, it indicates 115
C. If "nE", "00", and "28" are alternately displayed, it indicates -28
C.
If a parameter is invalid for the unit, ―00‖ is displayed.
If no button operations are performed on the master unit for five minutes, the function setting
automatically quits and the unit restores the current status.
Step 9: If the nb ODU bar code query is selected, the display is as follows. Enter the to-be-confirmed
status of ODU bar code query.
LED1
LED2
LED3
Function Code
Display Mode
Current Progress/Mode
Display Mode
Current Status
Display Mode
nb
Blinking
00
Blinking
00
Blinking
Press "SW7" on the master unit to enter the next-level menu selection. The display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
Module Address
Display Mode
Current Status
Display Mode
nb
On
01
Blinking
00
Blinking
nb
On
02
Blinking
00
Blinking
nb
On
03
Blinking
00
Blinking
nb
On
04
Blinking
00
Blinking
Select a module for query by pressing "SW1 (▲)" or "SW2 (▼)" and then press "SW7". The display is as
follows:
LED1
LED2
LED3
Function Code
Display Mode
Parameter Code
Display Mode
Current Status
Display Mode
nb
On
Un/Pc
Blinking
-n
Blinking
Note: Un indicates the entire-unit bar code and Pc indicates the controller bar code.
After confirming the module, select a bar code sequence by pressing "SW1 (▲)" or "SW2 (▼)". The
display sequence is as follows:
Entire-unit bar code (bits 1-13) and controller bar code (bits 1-13), that is, entire-
unit bar code header →
entire-unit bar code (bits 1-
6) → entire
-unit bar code (bits 7-
12) → entire
-
unit bar code (bit 13) →
controller bar code header → co
ntroller bar code (bits 1-
6) → controller bar code (bits 7
-
12) → controller
bar code (bit 13). The display is as follows:
LED1
LED2
LED3
Parameter Code
Display Mode
Parameter Code
Display Mode
Parameter Code
Display Mode
Code
On
Code
On
Code
On
Example:
Entire-unit bar code: N1R0128150066
Controller bar code: N1M0128150067
The display sequence is as follows:
LED1
LED2
LED3
Parameter Code
Display Mode
Parameter Code
Display Mode
Parameter Code
Display Mode
nb
On
Un
Blinking
-n
Blinking
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...