GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
130
C3
Communication
failure between
main control board
and variable
frequency fan drive
1. The communication cable is not
connected.
2. The communicator is
disconnected.
3. The communication cable is
poorly connected.
4. The communicator is faulty.
1) Check if the cable connecting the fan's drive board
and the compressor's drive board is loose. If yes,
reconnect it;
2) Check if the cable connecting the fan's drive board
and compressor's drive board is broken. If yes,
replace the cable;
3) Check the contact of the communication cable
connecting the fan's drive board and compressor's
drive board;
4) Replace the control board. If the fault is solved, the
control board is faulty. Replace the fan's drive
board. If the fault is solved, the fan's drive board is
faulty.
C5
Indoor unit project
number conflict
warning
1. Project numbers conflict with
each other.
1. Change conflicting project numbers and ensure
that no IDU's project number is repeated.
C6
Outdoor unit number
inconsistency
warning
1. Communication cables between
ODUs are loose.
2. Communication cables between
ODUs are broken.
3. Communication cables between
ODUs are poorly connected.
4. The control board is faulty.
1. If the communication cable is loose, reconnect it;
2. If the communication cable is broken, replace it;
3. Check contact of the communication cable;
4. Replace the control board.
CC
No controlling unit
1. The SA8 dial switch of the ODU
is not switched to 00.
2. The SA8 dial switch of the ODU
is faulty.
1. Switch the SA8 dial switch of an ODU to 00;
2. Replace the control board or switch an ODU's SA8
dial switch to 00.
CF
Multiple controlling
units
1. SA8 dial switches of multiple
ODUs are switched to 00.
2. Dial switches of multiple ODUs
are faulty.
1. Leave one SA8 dial switch unchanged, while
switch all the other dial switches to 11;
2. Replace the control board.
L7
No master IDU
1. The master IDU is powered off.
2. The communication of the master
IDU fails.
3. The main board of the master
IDU is faulty.
4. No master IDU is set in the
system.
1. Check if the master IDU is powered on. If yes,
replace the main board;
2. Check the contact of the communication cable of
the master IDU. If no communication failure (C0) is
reported, replace the main board.
3. Replace the IDU's main board and reset the
master IDU.
4. Set the master IDU.
C5
Project number
conflict
1. Multiple IDUs share one project
number.
1. Reset the repeated project number (useful when
there is no centralized control of multiple systems).
Note: Solution of C5 fault when multiple cooling systems are controlled in a centralized way
When multiple cooling systems are controlled in a centralized way, the C5 fault, i.e. project
number conflict, may occur on different cooling systems. In such case, set project numbers of
each system and solve the fault as follows:
1) Project number conflict:
When multiple systems are controlled in a centralized way, if two or more IDUs share the same
project number, the engineer number conflict occurs. In that case, IDUs cannot be switched to
varied modes or be turned on or off. The whole device cannot be started before the conflict is
solved. The commissioning software will show the following page:
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...