GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
123
system high-pressure value is
-15 to 5°C.
6
Opening
degree of
heating
electronic
expansion
valves
PLS
●During the cooling operation,
the heating electronic expansion
valves always remain at 480
PLS.
●During the heating operation,
the adjustable electronic
expansion valves change
between 120 and 480 PLS.
7
Operation
frequency of
inverter
compressor
Hz
●The operation frequency of
inverter compressor 1 changes
between 20 and 95 Hz.
●The operation frequency of
inverter compressor 2 changes
between 30 and 100 Hz.
8
Current of
inverter
compressor
A
●According to different oper
ation
frequencies and loads, the
current of inverter compressor 1
changes between 7 and 25 A.
The current of inverter
compressor 2 changes between 7
and 20 A.
9
IPM module
temperature of
inverter
compressor
°C
●When the environment
temperature is lower than 35°C,
the temperature of the IPM
module is lower than 80°C. The
highest temperature is not higher
than 95°C.
10
Driver bus line
voltage of
inverter
compressor
V
●The normal bus line voltage is
1.414 times larger than the
power voltage. For example, if
the three-phase power voltage is
390 V, the bus line voltage after
current rectification is 390 V ×
1.414 = 551 V. It is normal if the
difference between the actual
test value and the calculation
value is within 15 V.
11
Operation
frequency of
fan
Hz
●With the adjustment of system
pressure, the fans run between 0
and 65 Hz.
12
Indoor unit
parameter
Environment
temperature of
IDU
°C
——
13
Inlet-tube
temperature of
indoor heat
exchanger
°C
●As the environment
temperature is different, the
inlet-tube temperature is 1-7°C
lower than the outlet-tube
temperature of the same IDU in
cooling mode.
●The inlet
-tube temperature is
10-20°C lower than the
outlet-tube temperature of the
same IDU in heating mode.
14
Outlet-tube
temperature of
indoor heat
exchanger
°C
15
Opening
degree of
PLS
The opening degree
automatically changes between 0
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...