GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
177
Note: All wired controls are set to master wired controls by default.
(4) If the AP1 of the master IDU is replaced,
Reset the master IDU through the wired control; otherwise, the LCD displays L7 (no master IDU). There
are two methods to set the IDU:
①
In shut mode, press and hold the
―MODE‖
button for 5 seconds and set the IDU corresponding to this
wired control to a master IDU. After setting, the ―Main‖ icon is highlighted.
②
Set the wired control parameter ―P10‖ to 1.
3.2. Cautions on Wired Control XK49 Replacement
To replace the wired control XK49, in addition to the preceding handling steps specific for XK46, you
should also configure access control.
(1) If the wired control does not need an access control system, set switch ―1‖ for DIP S1 at the
bottom of
the wired control to digital end (neglect switch ―2‖).
(2) If the wired control needs an access control system, set switch ―1‖ for DIP S1 at the bottom of the
wired control to ON (neglect switch ―2‖) and connect the access control card interface
to ports N and L or
ports VCC and GND of the wiring terminal. The following should be noted:
①
Ports N and L are power interfaces of 100-240V~50/60Hz access control.
②
Ports VCC and GND are power interfaces of DC 5-24V access control.
③
Either of them can be selected at one time.
II. Compressor Replacement and Cautions
1. Determining Compressor Fault
1.1 Precondition: Units can be normally started.
Step 1:
If units can be normally started, start the units so as to measure line current of the faulty compressor.
Use a pressure gauge to measure pressure of various valves and connect the gauge to a PC for viewing
test data. Verify the current data in the figures below against the current recommended. For inverter
compressors, current will be deviated 10% while rate of turn and operating condition vary.
①
For inverter compressors E655DHD-65D2YG and E705DHD-72D2YG:
The figure below shows current curves that change with evaporating temperature and condensing
temperature while the compressors work at 30 Hz.
C
om
pr
es
so
r
C
ur
re
nt
(
A
)
Evaporating
Temp. (°C)
C
on
de
ns
in
g
T
em
p.
(
°C
)
The figure below shows current curves that change with evaporating temperature and condensing
temperature while the compressors work at 60 Hz.
C
om
pr
es
so
r
C
ur
re
nt
(
A
)
Evaporating
Temp. (°C)
C
on
de
ns
in
g
T
em
p.
(
°C
)
The figure below shows current curves that change with evaporating temperature and condensing
temperature while the compressors work at 90 Hz.
Содержание GMV-224WM/B-X
Страница 1: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL T1 R410A 50 60Hz GC201508...
Страница 6: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 3 2 Piping Diagram of GMV 400WM B X and GMV 450WM B X...
Страница 27: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 24...
Страница 29: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 26 V Construction Organization Process...
Страница 38: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 35...
Страница 45: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 42 Part 5 Piping Connection Schematic Diagram of Piping Connection...
Страница 47: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 44 GMV 504WM B X GMV 560WM B X and GMV 615WM B X...
Страница 156: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 153 low press ure air pipe...
Страница 158: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 155 2 Low exhaust temperature protection E2...
Страница 159: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 156 3 System high pressure protection E1 4 System low pressure protection E3...
Страница 160: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 157...
Страница 161: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 158 5 System refrigerant lacking protection U4...
Страница 162: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 159 6 System high pressure ratio protection J8...
Страница 163: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 160 7 System low pressure ratio protection J9...
Страница 165: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 162 11 Pressure sensor fault...
Страница 224: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 221 2 Model GMV 335WM B X Exploded View...
Страница 227: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 224 3 Model GMV 400WM B X GMV 450WM B X Exploded View...
Страница 230: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 227 4 Model GMV 504WM B X GMV 560WM B X GMV 615WM B X Exploded View...
Страница 242: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 239...
Страница 248: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 245 Click Finish...
Страница 250: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 247 Check I accept the terms in the License Agreement and click Next...
Страница 254: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 251 Click Next Installing...
Страница 255: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 252 Click Close...
Страница 272: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 269...
Страница 277: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 274 Power input Gateway Running Alarm Power Address Function...
Страница 287: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 284 1 4 2 5 Communication Debug...
Страница 297: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 294...
Страница 300: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 297 11 In the displayed window select I Agree and click Next to continue...
Страница 304: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 301...
Страница 307: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 304...
Страница 315: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 312 After detection detected devices will be listed in the Net tree...
Страница 349: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 346...
Страница 352: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 349 11 In the displayed window select I Agree and click Next to continue...
Страница 375: ...GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 372 JF00302751...