Installation & Service Manual
31
systems are matched to the destination country’s standard. For example, in the USA C19 to
NEMA 5-20P cables are provided.
USA Power Cable Example
About High Line (208V-240V) Versus Low Line (120V) Operations
North American users usually have a choice to use low line (120 volts) or high line (208-240
volts) as the AC source. If Low line is used, a 15RU Compact Frame with all options installed
and running at 120 volts will draw a total of approximately 15 amps from the line cords. At
100 volts, this increases to approximately 18 amps. This load will be evenly distributed
among the line cords.
IMPORTANT:
Each line cord must be serviced by a dedicated 20 amp
circuit. Two power supplies on the same circuit could exceed 20 amps.
With a fully loaded system, a third power supply is needed for
redundancy.
The possibility of drawing as much as 15 amps from a line cord explains the 20 amp
(NEMA 5-20P) plug on the line cords supplied. The NEC in the US specifies that the
ubiquitous 15 amp outlet be de-rated to 12 amps for continuous loads. A 20 amp outlet is
needed for the rare case of a 15 amp load experienced during a fault condition.
Most of the above is not an issue if high line (240V) operation is used. Since AC line currents
are approximately half of those at low line, exceeding the current rating of a circuit should
not be a problem. In areas where there is a choice between high line or low line operation,
the user should consider the advantages and disadvantages of each power sourcing
scheme.
About Low Line (120V) Operational Considerations
If low line (120V) operation is used (mostly in North America) three characteristics of
the switcher should be kept in mind when provisioning AC power for the system, which
will result in the most reliable system possible:
•
Consider brown-out—Modern switching power supplies are constant power
devices and as such, unlike resistive loads, the input current increases as the input
voltage decreases.
•
Consider power supply failure—If three or four power modules are present, they
will load share. For instance, if three modules are fitted and the total AC line
current is 10 amps, each of the three line cords will draw about 5 amps. If one
supply fails, the other
supply takes up the entire load. At this point, one line
cord will draw 0 amps and the other cord will draw 10 amps.
Consider future options—The total AC power consumption is significantly influenced by
the number and type of hardware options installed. This includes the number of boards:
DPMs, VPEs, I/Os, and Modular I/Os supply takes up the entire load.
8875_22
Содержание KARRERA
Страница 47: ...Installation Service Manual 23 15 RU Dimensions Side View ...
Страница 49: ...Installation Service Manual 25 15RUVideo Processor Views 15 RU Front View withDoor Removed ...
Страница 50: ...Frame Installation 26 15 RU Rear ViewIP Gearbox Conversion 15RU Front View withDoor Removed ...
Страница 52: ...Frame Installation 28 PowerSupplyFrameDimensions TopView ...
Страница 126: ...System Cabling GPI In GPI Out Relay Tally Pin Assignments 102 D 37Female Pin 1 Pin19 Pin 20 Pin 37 Socket Pinout ...
Страница 171: ...Installation Service Manual 147 ...
Страница 204: ...Basic Configuration 180 ...
Страница 208: ...Basic Configuration 184 green ...
Страница 234: ...Basic Configuration 210 ...
Страница 265: ...Installation Service Manual 241 ...
Страница 296: ...External Interfaces 272 PBus and GPI Enables ...
Страница 304: ...External Interfaces 280 About Editor Ports 6 Select the Map Sources button and configure the Switcher Sources ...
Страница 337: ...Installation Service Manual 313 8804_33 Karrera3 ME Panel Open Air Guide Removed Transition Input Board Board Power ...
Страница 366: ...Maintenance 342 ...
Страница 367: ...Installation Service Manual 343 ...
Страница 368: ...Maintenance 344 ...