Available Internal Data
3A6338F
17
If there is a step in operator mode throughout the active sequence, the EFR will only dispense that step if the Start
Current Sequence/Step, Trigger Operator Mode bit remains ON. Once the Start Current Sequence/Step, Trigger
Operator Mode bit is OFF, the EFR will continue with the active sequence.
Sending the Desired Active Sequence byte is optional. If the The Desired Active Sequence byte is not sent, the
current active sequence stored in the EFR will be used.
Automation Inputs (EFR Outputs)
System On
System Ready
Alarms Present
Deviations Present
Advisories Present
Dispensed Valve Open
Automation Outputs (EFR Inputs)
Start Current Sequence/Step, Trigger Operator Mode
System Enabled Request
Desired Active Sequence
EFR State
Sequence Running
Key
EFR Sequence is running
EFR Gateway Run Sequence in Operator Mode
"Desired Operator Mode Dispense Flow Rate" can be used to
modify flow rate on the fly during this time interval