Installation
4
3A6338F
5. Connect the CAN cable from either CAN connection
on the CGM to port 1 or port 2 on the EFR.
6. If used, connect the Ethernet, DeviceNet,
PROFINET, or PROFIBUS cable (FB) to the CGM
as applicable. Connect the other end of the cable to
the fieldbus device.
7. Reinstall the pump yoke shroud (F) and the frame
cover (G) onto the EFR system.
8. Using token 19A534, perform the Install or Update
Data Map procedure in the Communications
Gateway Module, Instructions – Parts manual. See
9. Perform the
procedure on page 5 to
configure the fieldbus.
NOTE:
To produce an accurate dispense, the dispense
valve must be controlled directly by the EFR. See the
Electric Fixed Ratio Proportioner, Setup - Operation
manual for I/O integration of the dispense valve with the
EFR.
NOTE:
Automation Outputs (signals from PLC
on page 25 for information on
triggering a dispense through the EFR using the CGM.
To produce accurate starts/stops, it is recommended to
use discrete I/O to trigger a dispense. See the Electric
Fixed Ration Proportioner, Setup-Operation manual for
instructions on I/O integration of the triggering signal.
NOTICE
Ensure the CAN cable is connected to an appropriate
CAN connection. Failure to connect the CAN cable
correctly can result in damage to the CGM module.
F
IG
. 5: Cable Connections
F
IG
. 6: Cable Connections
CAN
Connector 1
ti11972a
CAN
Connector 2
ti11985a