20
G
G
G
G
G
A S
A S
A S
A S
A S
S
S
S
S
S
U P P L
U P P L
U P P L
U P P L
U P P LY
Y
Y
Y
Y
A N D
A N D
A N D
A N D
A N D
P
P
P
P
P
I P I N G
I P I N G
I P I N G
I P I N G
I P I N G
•
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from 1/
2 inch to another pipe size.
C
C
C
C
C
OUNTERFLOW
OUNTERFLOW
OUNTERFLOW
OUNTERFLOW
OUNTERFLOW
I
I I
I
I
NSTALLATIONS
NSTALLATIONS
NSTALLATIONS
NSTALLATIONS
NSTALLATIONS
When the gas piping enters through the left side of the furnace, the
installer must supply a straight pipe and a 90 degree elbow to reach
the exterior of the furnace.
A ground joint union, drip leg and manual shutoff valve must also
be supplied by the installer. In most cases, the installer may also
need to supply a transition piece from ½” to another pipe size.
When the gas piping enters through the right side of the furnace,
the installer must supply the following fittings (starting at the gas
valve):
•
Close Nipple
•
90 Degree Elbow
•
Straight Pipe to Reach Exterior of Furnace.
G
G
G
G
G
AS
AS
AS
AS
AS
P
P
P
P
P
IPING
IPING
IPING
IPING
IPING
C
C
C
C
C
HECKS
HECKS
HECKS
HECKS
HECKS
Before placing unit in operation, leak test the unit and gas connec-
tions.
T
O
AVOID
THE
POSSIBILITY
OF
EXPLOSION
OR
FIRE
,
NEVER
USE
A
MATCH
OR
OPEN
FLAME
TO
TEST
FOR
LEAKS
.
WARNING
Check for leaks using an approved chloride-free soap and water
solution, an electronic combustible gas detector, or other approved
testing methods.
NOTE:
NOTE:
NOTE:
NOTE:
NOTE: Never exceed specified pressures for testing. Higher pressure
may damage the gas valve and cause subsequent overfiring, resulting
in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping
system before pressure testing the supply piping system with pres-
sures in excess of 1/2 psig (3.48 kPa).
This unit must be isolated from the gas supply system by closing its
manual shutoff valve before pressure testing of gas supply piping
system with test pressures equal to or less than 1/2 psig (3.48 kPa).
P
P
P
P
P
ROPANE
ROPANE
ROPANE
ROPANE
ROPANE
G
G
G
G
G
AS
AS
AS
AS
AS
T
T
T
T
T
ANKS
ANKS
ANKS
ANKS
ANKS
AND
AND
AND
AND
AND
P
P
P
P
P
IPING
IPING
IPING
IPING
IPING
I
F
THE
GAS
FURNACE
IS
INSTALLED
IN
A
BASEMENT
,
AN
EXCAVATED
AREA
OR
CONFINED
SPACE
,
IT
IS
STRONGLY
RECOMMENDED
TO
CONTACT
A
PROPANE
SUPPLIER
TO
INSTALL
A
GAS
DETECTING
WARNING
DEVICE
IN
CASE
OF
A
GAS
LEAK
.
S
INCE
PROPANE
GAS
IS
HEAVIER
THAN
AIR
,
ANY
LEAKING
GAS
CAN
SETTLE
IN
ANY
LOW
AREAS
OR
CONFINED
SPACES
.
P
ROPANE
GAS
ODORANT
MAY
FADE
,
MAKING
THE
GAS
UNDETECTABLE
EXCEPT
WITH
A
WARNING
DEVICE
.
•
•
WARNING
A gas detecting warning system is the only reliable way to detect a
propane gas leak. Rust can reduce the level of odorant in propane
gas. Do not rely on your sense of smell. Contact a local propane gas
supplier about installing a gas detecting warning system. If the
presence of gas is suspected, follow the instructions on Page 3 of
this manual.
All propane gas equipment must conform to the safety standards of
the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 10 inch
WC at the furnace manifold with all gas appliances in operation.
Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liquid,
and “wetted surface” area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size will
depend on length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vaporization, rec-
ommended regulator settings, and pipe sizing is available from
most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most stan-
dard commercial compounds, special pipe dope must be used.
Shellac-based compounds resistant to the actions of liquefied pe-
troleum gases such as Gasolac
®
, Stalactic
®
, Clyde’s
®
or John Crane
®
are satisfactory.
Refer to the following illustration for typical propane gas installa-
tions and piping.
200 PSIG
Maximum
5 to 15 PSIG
(20 PSIG Max.)
Continuous
11" W.C.
Second Stage
Regulator
First Stage
Regulator
Propane Gas Installation (Typ.)
Содержание GDVC80703B
Страница 46: ...46 THIS PAGE LEFT BLANK INTENTIONALLY...
Страница 47: ...47 THIS PAGE LEFT BLANK INTENTIONALLY...