GEFRAN
——————
Interface Board DeviceNet
——————
50
5.2.6.2.3 Read Single Virtual Digital Output Configuration - Reply Error
If the reading of the single configuration of the “Virtual Digital Outputs” is rejected,
the response is the following:
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
14hex OR
80hex
Get _Attribute_Single Reply
code- Common Service.
1Fhex
Error vendor specific (see
Additional field)
<> 1Fhex
DeviceNet specific error
code (see DeviceNet
Specifications).
Additional
XX
1)
Drive specific error code.
dn4105
Byte
General
Error
1)
For error codes see chapter 6.0.
5.2.6.2.4 Read Entire Virtual Digital Output Configuration
The data frame for the reading of the entire configuration of the “Virtual Digital
Outputs” is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
01hex
Get_Attribute_All - Common
Service
Class ID
6Bhex
Virtual Digital Output
Configuration Class Object
Instance ID
01
Virtual Digital Output Instance
ID
dn5160
See Note
1)
1)
Byte or Words depending on the type of allocation executed by the Master.
5.2.6.2.5 Read Entire Virtual Digital Output Configuration - Reply OK
If the entire configuration of the “Virtual Digital Outputs” is read correctly, the re-
sponse is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
01hex OR
80hex
Get_Attribute_All Reply code-
Common Service
Word 0 Virtual
Digital Output
Drive parameter index assigned to the
Virtual Digital Output first word.
Word xx Virtual
Digital Output
Drive parameter index assigned to the
Virtual Digital Output xxth word.
Word 15 Virtual
Digital Output
Drive parameter index assigned to the
Virtual Digital Output 16th word.
dn5170
Word
XXXX
1)
1)
The format of the Drive parameter index is Low Byte - High byte.