GEFRAN
——————
Interface Board DeviceNet
——————
30
4.1.6.1.5 Write Entire Polling S->M Configuration - Reply OK
If the entire configuration of the Polling S->M is written correctly, the response is
composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
02hex OR
80hex
Set_Attribute_All Reply
code- Common Service.
General
Error
00
Additional
00
dn4070
Byte
Zero means service correctly
executed.
4.1.6.1.6 Write Entire Polling S->M Configuration - Reply Error
If the writing of the entire configuration of the Polling S->M is rejected, the response
is the following:
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
14hex OR 80hex
Set _Attribute_ All Reply code-
Common Service
1Fhex
Error vendor specific (see
Additional field)
<> 1Fhex
DeviceNet specific error code
(see DeviceNet Specifications)
Additional
XX
1)
Drive specific error code.
dn4080
Byte
General
Error
1)
For error codes see chapter 6.0
4.1.6.2 Read S->M Polling Configuration
In this example is shown the reading of the configuration of the Polling S->M; the
cases of positive and wrong reading are distinguished.
4.1.6.2.1 Read Single Polling S->M Configuration
The data frame for the reading of the single configuration of the Polling S->M is
composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
0Ehex
Get_Attribute_Single -
Common Service
Class ID
68hex
Polling S ->M Configuration
Class Object
Instance ID
01
Polling S ->M Instance ID
Byte
Attribute ID
XX
Polling S ->M word involved
in configuration
dn4090
See Note
1)
1)
Byte or Word depending on the type of allocation executed by the Master.