
GEFRAN
——————
Interface Board DeviceNet
——————
44
5.1.6.2.3 Read Single Virtual Digital Input Configuration - Reply Error
If the reading of the single configuration of the “Virtual Digital Inputs” is rejected,
the response is the following:
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
14hex OR
80hex
Get _Attribute_Single Reply
code- Common Service.
1Fhex
Error vendor specific (see
Additional field)
<> 1Fhex
DeviceNet specific error
code (see DeviceNet
Specifications).
Additional
XX
1)
Drive specific error code.
dn4105
Byte
General
Error
1)
For error codes see chapter 6.0.
5.1.6.2.4 Read Entire Virtual Digital Input Configuration
The data frame for the reading of the entire configuration of the “Virtual Digital
Inputs” is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
01hex
Get_Attribute_All - Common
Service.
Class ID
6Ahex
Virtual Digital I/O
Configuration Class Object
Instance ID
01
Virtual Digital Input Instance
ID
dn5070
See Note
1)
1)
Byte or Word depending on the type of allocation executed by the Master.
5.1.6.2.5 Read Entire Virtual Digital Input Configuration - Reply OK
If the entire configuration of the “Virtual Digital Inputs” is read correctly, the response
is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
01hex OR
80hex
Get_Attribute_All Reply code-
Common Service
Word 0 Virtual
Digital Input
Drive parameter index assigned to
the Virtual Digital Input first word
Word xx Virtual
Digital Input
Drive parameter index assigned to
the Virtual Digital Input xx th word
Word 15 Virtual
Digital Input
Drive parameter index assigned to
the Virtual Digital Input 16th word
dn5080
Word
XXXX
1)
1)
The format of the Drive parameter index is Low Byte - High byte.