SBI-DN
43
——————
Interface Board DeviceNet
——————
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
14hex OR
80hex
Set _Attribute_Single Reply
code- Common Service.
1Fhex
Error vendor specific (see
Additional field)
<> 1Fhex
DeviceNet specific error
code (see DeviceNet
Specifications).
Additional
XX
1)
Drive specific error code.
dn4050
Byte
General
Error
1)
For error codes see chapter 6.0.
5.1.6.2 Read Virtual Digital Input Configuration
In this example is shown the reading of the configuration of the “Virtual Digital Inputs”;
the cases of positive and wrong reading are distinguished.
5.1.6.2.1 Read Single Virtual Digital Input Configuration
The data frame for the reading of the single configuration of the “Virtual Digital
Inputs” is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
0Ehex
Get_Attribute_Single - Common
Service.
Class ID
6Ahex
Virtual Digital I/O
Configuration Class Object
Instance ID
01
Virtual Digital Input Instance
ID
Byte
Attribute ID
XX
Virtual Digital Input XX word
involved in the configuration
dn5050
See Note
1)
1)
Byte or Word depending on the type of allocation executed by the Master.
5.1.6.2.2 Read Single Virtual Digital Input Configuration - Reply OK
If the single configuration of the “Virtual Digital Inputs” is read correctly, the response
is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
0Ehex OR
80hex
Get_Attribute_Single Reply code-
Common Service.
Word
Word 0 Virtual
Digital Input
XXXX
1)
Drive parameter index assigned to
the Virtual Digital Input XX
word.
dn5060
1)
The format of the Drive parameter index is Low Byte - High byte.