Interface Board DeviceNet
——————
12
Switch 8
Switch 7
Baud Rate
OFF
OFF
125 kBaud
OFF
ON
250 kBaud
ON
OFF
500 kBaud
ON
ON
125 KBaud
DN21
5. The dip switch S1 determines the Slave address. The address “0” is reserved
to the Master and it must not be used. The switches S1 -7 and S1-8 do not
determine any address. The address is detected only when the board is swi-
tched on. If the address is modified, the Drive has to be switched off and then
switched on in order to assume the new address.
6. Connect the Bus cable to the BUS connection terminal.
7. Switch on the drive.
8. The LEDS PWR and RUN light up.
9. Switch the Device Net power supply on; the LED H1 lights up.
10. The LED OP lights up when the Master/Slave connection has been established.
WARNING: Replace all covers before applying power to the Drive. Failure to
do so may result in death or serious injury.
11. Replace the upper and lower cover by performing the procedures described
in step 1. in the reverse order.
12. To restore the warranty seal, apply the WARRANTY-R label to the TPD32-.EV
converter over the label broken during opening.
Warranty-R label:
2.3 POWER SUPPLY
The power supply is provided by the XO connector, which is used to connect the
data between the SBI board and the Drive regulation board.
Absorbed current: 350 mA