6. Control Functions and Parameter Settings
6-25
Block-C parameters (Basic function constants) list
Application
No.
Parameter
Unit
Default
Min.
Max.
Function
ST
V/f VEC PM
C11 – Operation panel mode setting
0
Initial mode
1.
1.
2.
The initial operation mode for when
the power is turned ON is set
= 1 : Local
= 2 : Remote
1
Run command status
1.
1.
3.
This is the initial operation mode at
power ON, during local operation
mode (operation from operation
panel) if the automatic start function
(C08-0 =2 or 3) is enabled.
.
= 1 : Stop = 2 : Forward run
= 3 : Reverse run
3
Operation panel
monitor settings
0.0
0.0
99.9
Set the monitor parameter No. to be
displayed initially when the power is
turned ON.
C12 – Setting input terminal function
0
FSV terminal input
mode
1.
1.
3.
1: 0 ~ 10V, 2: 0 ~ 5V, 3: 1 ~ 5V
1
FSI terminal input
mode
1.
1.
2.
1: 4 ~ 20mA, 2: 0 ~ 20mA
2
AUX terminal input
mode
1.
1.
3.
1: 0 ~ ±10V, 2: 0 ~ ±5V, 3: 1 ~ 5V
3
Filter time constant for
FSV/FSI and AUX
input
1.
1.
2.
1: 8ms 2: 32ms
4
AUX input gain
1.000
0.000
5.000
C13 – Output terminal function
0
FM output settings
0.
0.
9.
1
AM output settings
3.
0.
9.
Select the setting value from the
following table, and output.
The terminal voltage can be changed
freely with parameters C14-0.1
2
RC-RA output settings
0.
0.
24.
3
PSO1 output settings
3.
0.
24.
4
PSO2 output settings
7.
0.
24.
5
PSO3 output settings
8.
0.
24.
Select the setting value from the
following table, and output.
Value
Parameter
Output Voltage
0
Output frequency
10V at max. frequency
1
Setting frequency
Setting Speed
10V at max. frequency
10V at max. speed
2
Ramp output
10V at max. frequency
10V at max. speed
3
Output current (motor)
5V at motor rated current
4
Output current (drive)
5V at drive rated current
5
Output Voltage
10V at rated Voltage
6
Output power (drive)
5V at motor rated power
7
DC Voltage
5V at 300V (200V Series)
5V at 600V (400V Series)
8
OLT Monitor
10V at 100%
9
Heatsink Temperature
10V at 100ºC
10
Motor speed
10V at max. speed
Value
Output
signal
Value
Output
signal
Value
Output
signal
Value
Output
signal
0
RUN
8
ATN
16
ACC
24
ULMT
1
FLT
9
SPD1
17
DCC
2
MC
10
SPD2
18
AUXDV
3
RDY1
11
COP
19
ALM
4
RDY2
12
EC0
20
FAN
5
LCL
13
EC1
21
ASW
6
REV
14
EC2
22
ZSP
7
IDET
15
EC3
23
LLMT