2. Installation and Wiring
2-8
2-4 Precautions for Wiring to the Control Signal
1)
Separate the main circuit wiring (to terminals L1, L2, L3, L+1, L+2, L–, B, U, V, W) from the other
drive wires and power wires.
2)
Use a 0.25 to 0.75mm² wire for wiring to the control circuit. The tightening torque must be 0.6Nm.
3)
Use a twisted pair wire or twisted pair shield wire for wiring the analog signals (as the setters and meter).
(Fig. 2-6.) Connect the shield wire to the TB2 COM terminal of the VAT2000.
The wire length must be 30m or less.
4)
The analog output is dedicated for metering only, such as the speed-meter and ammeter.
It cannot be used for control signals such as the feedback control.
5)
The length of the sequence input/output contact wire must be 50m or less.
6)
The sequence input (digital I/Os), can be selected either sink logic or source logic method by the
short pin (W1). Refer to Table 5-2.
7)
Observe the precautions listed in "Table 5-2 Control input/output circuit".
8)
An example of the control circuit wiring is given in Fig. 2-6.
9)
The layout of the control circuit terminal block is shown in Fig. 2-7; functions are in Table 5-1.
Terminals with the same terminal symbol are internally connected.
10) After wiring, always check the wiring. Do not test control wirings using a megger or buzzer
R E S E T
C O M
A U X
F S I
F S V
P 1 0
2 0K
+ 1 5 V
8 20
Ω
2 44
Ω
2 0K
F M
A M
C O M
C O M
Vo ltag e
o utp ut
(0 -10 V )
lo ad
m ax . 1m A
R A
R C
FA
F B
F C
P S O 1
P S O E
VAT 2000
M ax . 1A 25 0VA C
o r 30 V D C
M ax . 0,4 A 2 50 V A C
o r 1A 3 0V D C
O pe n c ollec to r
M ax . 30 V D C 3 0m A
0 V
0 V
E M S
R U N
P S I1
(R R U N )
(F J O G )
(R J O G )
S tan da rd S ettin g
P S I2
P S I3
P S I4
P S I5
R Y O
R Y O V (N o te 2 )
A N A L O G IN PU T
D IG ITA L IN P U T
F re q ue nc y
s ettin g (vo lta ge )
2 K
, 2 W
F re q ue nc y
S e ttin g (c urren t)
A u x. s ettin g
D C ± 10 V
C o m m o n
Ω
F re e Vo lta ge inp ut
(5 m A pe r s ig na l)
R Y 24
4 .7K
F
A
To c o m p ly
w ith U L
u se a t
3 0VA C /D C
o r lo w er
P S O 2
P S O E
R Y 24
R Y 2 4V
P S O 3
(Notes)
1.
Three COM terminals are internally connected.
2.
No connection shall be made between RY0 and COM since this section is insulated.
3.
This diagram is an example of the sink logic connection. (Refer to Table 5-2.)
Fig. 2-6
• Control terminal (The terminal block is laid out in two rows.)
TB1
TB2
RY24 RESET PSI1
PSI2
PSI4
PSO1 PSOE
PI0
COM
AUX
AM
FM
RC
FA
RUN
EMS
RY0
PSI3
PSI5
PSO2 PSO3
FSV
FSI
COM
COM
RA
FC
FB
Fig. 2-7
1
2
3
W1