GE Multilin
L60 Line Phase Comparison System
B-35
APPENDIX B
B.4 MEMORY MAPPING
B
70B0
...Repeated for Phase Distance Zone 3
Ground Distance (Read/Write Grouped Setting) (5 modules)
7130
Ground Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7131
Ground Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7132
Ground Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
7133
Ground Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
7134
Ground Distance Zone 1 Comparator Limit
30 to 90
degrees
1
F001
90
7135
Ground Distance Zone 1 Delay
0 to 65.535
s
0.001
F001
0
7136
Ground Distance Zone 1 Block
0 to 65535
---
1
F300
0
7137
Ground Distance Zone 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7138
Ground Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
7139
Ground Distance Zone 1 Shape
0 to 1
---
1
F120
0 (Mho)
713A
Ground Distance Zone 1 Z0 Z1 Magnitude
0 to 10
---
0.01
F001
270
713B
Ground Distance Zone 1 Z0 Z1 Angle
-90 to 90
degrees
1
F002
0
713C
Ground Distance Zone 1 RCA
30 to 90
degrees
1
F001
85
713D
Ground Distance Zone 1 DIR RCA
30 to 90
degrees
1
F001
85
713E
Ground Distance Zone 1 DIR Comp Limit
30 to 90
degrees
1
F001
90
713F
Ground Distance Zone 1 Quad Right Blinder
0.02 to 500
ohms
0.01
F001
1000
7140
Ground Distance Zone 1 Quad Right Blinder RCA
60 to 90
degrees
1
F001
85
7141
Ground Distance Zone 1 Quad Left Blinder
0.02 to 500
ohms
0.01
F001
1000
7142
Ground Distance Zone 1 Quad Left Blinder RCA
60 to 90
degrees
1
F001
85
7143
Ground Distance Zone 1 Z0M Z1 Magnitude
0 to 7
---
0.01
F001
0
7144
Ground Distance Zone 1 Z0M Z1 Angle
-90 to 90
degrees
1
F002
0
7145
Ground Distance Zone 1 Voltage Level
0 to 5
pu
0.001
F001
0
7146
Ground Distance Zone 1 Non-Homogeneous Angle
-40 to 40
degrees
0.1
F002
0
7147
Ground Distance Zone 1 POL Current
0 to 1
---
1
F521
0 (Zero-seq)
7148
Ground Distance Zone 1 Reverse Reach
0.02 to 500
ohms
0.01
F001
200
7149
Ground Distance Zone 1 Reverse Reach RCA
30 to 90
degrees
1
F001
85
714A
Reserved (7 items)
0 to 65535
---
1
F001
0
7151
...Repeated for Ground Distance Zone 2
7172
...Repeated for Ground Distance Zone 3
Line Pickup (Read/Write Grouped Setting)
71F0
Line Pickup Function
0 to 1
---
1
F102
0 (Disabled)
71F1
Line Pickup Signal Source
0 to 5
---
1
F167
0 (SRC 1)
71F2
Line Pickup Phase IOC Pickup
0 to 30
pu
0.001
F001
1000
71F3
Line Pickup UV Pickup
0 to 3
pu
0.001
F001
700
71F4
Line End Open Pickup Delay
0 to 65.535
s
0.001
F001
150
71F5
Line End Open Reset Delay
0 to 65.535
s
0.001
F001
90
71F6
Line Pickup OV Pickup Delay
0 to 65.535
s
0.001
F001
40
71F7
Autoreclose Coordination Pickup Delay
0 to 65.535
s
0.001
F001
45
71F8
Autoreclose Coordination Reset Delay
0 to 65.535
s
0.001
F001
5
71F9
Autoreclose Coordination Bypass
0 to 1
---
1
F102
1 (Enabled)
71FA
Line Pickup Block
0 to 65535
---
1
F300
0
71FB
Line Pickup Target
0 to 2
---
1
F109
0 (Self-reset)
71FC
Line Pickup Events
0 to 1
---
1
F102
0 (Disabled)
71FD
Terminal Open
0 to 65535
---
1
F300
0
71FE
Autoreclose Accelerate
0 to 65535
---
1
F300
0
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260
Phase Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7261
Phase Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7262
Phase Directional Overcurrent 1 Block
0 to 65535
---
1
F300
0
7263
Phase Directional Overcurrent 1 ECA
0 to 359
---
1
F001
30
7264
Phase Directional Overcurrent 1 Pol V Threshold
0 to 3
pu
0.001
F001
700
7265
Phase Directional Overcurrent 1 Block Overcurrent
0 to 1
---
1
F126
0 (No)
Table B–9: MODBUS MEMORY MAP (Sheet 27 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...