GE Multilin
L60 Line Phase Comparison System
5-149
5 SETTINGS
5.5 GROUPED ELEMENTS
5
•
POWER SWING MODE:
This setting selects between the two-step and three-step operating modes and applies to
both power swing blocking and out-of-step tripping functions. The three-step mode applies if there is enough space
between the maximum load impedances and distance characteristics of the relay that all three (outer, middle, and
inner) characteristics can be placed between the load and the distance characteristics. Whether the spans between
the outer and middle as well as the middle and inner characteristics are sufficient should be determined by analysis of
the fastest power swings expected in correlation with settings of the power swing timers.
The two-step mode uses only the outer and inner characteristics for both blocking and tripping functions. This leaves
more space in heavily loaded systems to place two power swing characteristics between the distance characteristics
and the maximum load, but allows for only one determination of the impedance trajectory.
•
POWER SWING SUPV:
A common overcurrent pickup level supervises all three power swing characteristics. The
supervision responds to the positive sequence current.
•
POWER SWING FWD REACH:
This setting specifies the forward reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system consisting of a line and two equivalent sources, this reach should be
higher than the sum of the line and remote source positive-sequence impedances. Detailed transient stability studies
may be needed for complex systems in order to determine this setting. The angle of this reach impedance is specified
by the
POWER SWING FWD RCA
setting.
•
POWER SWING QUAD FWD REACH MID
: This setting specifies the forward reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the
POWER SWING FWD RCA
setting. The setting is not used if
the shape setting is “Mho”.
•
POWER SWING QUAD FWD REACH OUT
: This setting specifies the forward reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the
POWER SWING FWD RCA
setting. The setting is not used if
the shape setting is “Mho”.
•
POWER SWING FWD RCA:
This setting specifies the angle of the forward reach impedance for the mho characteris-
tics, angles of all the blinders, and both forward and reverse reach impedances of the quadrilateral characteristics.
•
POWER SWING REV REACH:
This setting specifies the reverse reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system of a line and two equivalent sources, this reach should be higher than
the positive-sequence impedance of the local source. Detailed transient stability studies may be needed for complex
systems to determine this setting. The angle of this reach impedance is specified by the
POWER SWING REV RCA
setting
for “Mho”, and the
POWER SWING FWD RCA
setting for “Quad”.
•
POWER SWING QUAD REV REACH MID
: This setting specifies the reverse reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the
POWER SWING FWD RCA
setting. The setting is not used if
the shape setting is “Mho”.
•
POWER SWING QUAD REV REACH OUT
: This setting specifies the reverse reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the
POWER SWING FWD RCA
setting. The setting is not used if
the shape setting is “Mho”.
•
POWER SWING REV RCA:
This setting specifies the angle of the reverse reach impedance for the mho characteris-
tics. This setting applies to mho shapes only.
•
POWER SWING OUTER LIMIT ANGLE:
This setting defines the outer power swing characteristic. The convention
depicted in the
Power swing detect characteristic
diagram should be observed: values greater than 90° result in an
apple-shaped characteristic; values less than 90° result in a lens shaped characteristic. This angle must be selected in
consideration of the maximum expected load. If the maximum load angle is known, the outer limit angle should be
coordinated with a 20° security margin. Detailed studies may be needed for complex systems to determine this setting.
This setting applies to mho shapes only.
•
POWER SWING MIDDLE LIMIT ANGLE:
This setting defines the middle power swing detect characteristic. It is rele-
vant only for the 3-step mode. A typical value would be close to the average of the outer and inner limit angles. This
setting applies to mho shapes only.
•
POWER SWING INNER LIMIT ANGLE:
This setting defines the inner power swing detect characteristic. The inner
characteristic is used by the out-of-step tripping function: beyond the inner characteristic out-of-step trip action is defi-
nite (the actual trip may be delayed as per the
TRIP MODE
setting). Therefore, this angle must be selected in consider-
ation to the power swing angle beyond which the system becomes unstable and cannot recover.
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...