GE Multilin
L60 Line Phase Comparison System
5-15
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.4 COMMUNICATIONS
a) MAIN MENU
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
b) SERIAL PORTS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
Ö
SERIAL PORTS
The L60 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port is RS485. The RS485 ports have settings for baud rate and parity. It is important that
these parameters agree with the settings used on the computer or other equipment that is connected to these ports. Any of
COMMUNICATIONS
SERIAL PORTS
See below.
MESSAGE
NETWORK
MESSAGE
MODBUS PROTOCOL
MESSAGE
DNP PROTOCOL
MESSAGE
DNP / IEC104
POINT LISTS
MESSAGE
IEC 61850 PROTOCOL
MESSAGE
WEB SERVER
HTTP PROTOCOL
MESSAGE
TFTP PROTOCOL
MESSAGE
IEC 60870-5-104
PROTOCOL
MESSAGE
SNTP PROTOCOL
MESSAGE
ETHERNET SWITCH
SERIAL PORTS
RS485 COM1 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
MESSAGE
RS485 COM1 PARITY:
None
Range: None, Odd, Even
Only active if CPU Type E is ordered
MESSAGE
RS485 COM1 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
Only active if CPU Type E is ordered
MESSAGE
RS485 COM2 BAUD
RATE: 19200
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
MESSAGE
RS485 COM2 PARITY:
None
Range: None, Odd, Even
MESSAGE
RS485 COM2 RESPONSE
MIN TIME:
0 ms
Range: 0 to 1000 ms in steps of 10
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...