GE Multilin
L60 Line Phase Comparison System
B-29
APPENDIX B
B.4 MEMORY MAPPING
B
605D
Wattmetric ground fault 1 target
0 to 2
---
1
F109
0 (Self-reset)
605E
Wattmetric ground fault 1 events
0 to 1
---
1
F102
0 (Disabled)
605F
Wattmetric ground fault 1 reference power
0.001 to 1.2
pu
0.001
F001
500
6060
Reserved
---
---
---
---
---
6061
...Repeated for wattmetric ground fault 2
Wattmetric ground fault actual values (read only)
6072
Wattmetric ground fault 1 operating power
0.000 to 1000000.000
W
0.001
F060
0
6074
Wattmetric ground fault 2 operating power
0.000 to 1000000.000
W
0.001
F060
0
Phase comparison: negative-sequence voltage fault detection settings (read/write, grouped)
6080
Negative-sequence voltage fault detector function
0 to 1
---
1
F102
0 (Disabled)
6081
Negative-sequence voltage fault detector impedance
0 to 100
%
.01
F001
100
6082
Negative-sequence voltage fault detector low pickup
0.005 to 3.000
pu
0.001
F001
10
6083
Negative-sequence voltage fault detector high pickup
0.005 to 3.000
pu
0.001
F001
50
6084
Negative-sequence voltage fault detector block
0 to 65535
---
1
F300
0
6085
Negative-sequence voltage fault detector target
0 to 2
---
1
F109
0 (Self-reset)
6086
Negative-sequence voltage fault detector events
0 to 1
---
1
F102
0 (Disabled)
Phase comparison: rate of change of negative-sequence current settings (read/write, grouped)
6088
Negative-sequence current rate of change function
0 to 1
---
1
F102
0 (Disabled)
6089
Negative-sequence current rate of change low pickup
0.01 to 5.00
pu
0.01
F001
10
608A
Negative-sequence current rate of change low seal-in
0 to 10.000
s
0.001
F001
600
608B
Negative-sequence current rate of change high pickup
0.01 to 5.00
pu
0.01
F001
50
608C
Negative-sequence current rate of change high seal-in
0 to 10.000
s
0.001
F001
200
608D
Negative-sequence current rate of change supervision
0 to 65535
---
1
F300
0
608E
Negative-sequence current rate of change block
0 to 65535
---
1
F300
0
608F
Negative-sequence current rate of change target
0 to 2
---
1
F109
0 (Self-reset)
6090
Negative-sequence current rate of change events
0 to 1
---
1
F102
0 (Disabled)
Phase comparison: rate of change of positive-sequence current settings (read/write, grouped)
6091
Positive-sequence current rate of change function
0 to 1
---
1
F102
0 (Disabled)
6092
Positive-sequence current rate of change low pickup
0.01 to 5.00
pu
0.01
F001
10
6093
Positive-sequence current rate of change low seal-in
0 to 10.000
s
0.001
F001
600
6094
Positive-sequence current rate of change high pickup
0.01 to 5.00
pu
0.01
F001
50
6095
Positive-sequence current rate of change high seal-in
0 to 10.000
s
0.001
F001
200
6096
Positive-sequence current rate of change supervision
0 to 65535
---
1
F300
0
6097
Positive-sequence current rate of change block
0 to 65535
---
1
F300
0
6098
Positive-sequence current rate of change target
0 to 2
---
1
F109
0 (Self-reset)
6099
Positive-sequence current rate of change events
0 to 1
---
1
F102
0 (Disabled)
Phase comparison negative-sequence current fault detector (read/write grouped settings)
60A0
Negative-sequence current fault detector function
0 to 1
---
1
F102
0 (Disabled)
60A1
Negative-sequence current fault detector low pickup
0.02 to 5
pu
0.01
F001
10
60A2
Negative-sequence current fault detector high pickup
0.05 to 15
pu
0.01
F001
50
60A3
Negative-sequence current fault detector block
0 to 65535
---
1
F300
0
60A4
Negative-sequence current fault detector target
0 to 2
---
1
F109
0 (Self-reset)
60A5
Negative-sequence current fault detector events
0 to 1
---
1
F102
0 (Disabled)
Phase comparison positive-sequence current fault detector (read/write grouped settings)
60A8
Positive-sequence current fault detector function
0 to 1
---
1
F102
0 (Disabled)
60A9
Positive-sequence current fault detector low pickup
0.02 to 5
pu
0.01
F001
50
60AA
Positive-sequence current fault detector high pickup
0.05 to 15
pu
0.01
F001
75
60AB
Positive-sequence current fault detector block
0 to 65535
---
1
F300
0
60AC
Positive-sequence current fault detector target
0 to 2
---
1
F109
0 (Self-reset)
60AD
Positive-sequence current fault detector events
0 to 1
---
1
F102
0 (Disabled)
Phase Comparison Open Breaker Keying (Read/Write Grouped Setting)
60E0
Open Breaker Keying
0 to 1
---
1
F102
0 (Disabled)
60E1
Breaker 1 Auxiliary Contact
0 to 65535
---
1
F300
0
60E2
Breaker 1 Supervision Element
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...