5 SETTINGS
5.5 GROUPED ELEMENTS
5
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
The phase quadrilateral distance function is comprised of a reactance characteristic, right and left blinders, and 100%
memory-polarized directional and current supervising characteristics. When set to “Non-directional”, the quadrilateral func-
tion applies a reactance line in the reverse direction instead of the directional comparators. Refer to Chapter 8 for additional
information.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1.
The
SIGNAL SOURCE
setting (common for the distance elements of all zones as entered under
SETTINGS
ÖØ
GROUPED
ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
DISTANCE
).
2.
The
MEMORY DURATION
setting (common for the distance elements of all zones as entered under
SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
DISTANCE
).
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8:
Theory of operation
.
Although all zones can be used as either instantaneous elements (pickup [
PKP
] and dropout [
DPO
] FlexLogic™ operands)
or time-delayed elements (operate [
OP
] FlexLogic™ operands), only zone 1 is intended for the instantaneous under-reach-
ing tripping mode.
Ensure that the
PHASE VT SECONDARY VOLTAGE
setting (see the
SETTINGS
ÖØ
SYSTEM SETUP
Ö
AC INPUTS
ÖØ
VOLTAGE BANK
menu) is set correctly to prevent improper operation of associated memory action.
•
PHS DIST Z1 DIR:
All phase distance zones are reversible. The forward direction is defined by the
PHS DIST Z1 RCA
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the
PHS DIST Z1 REACH
and
PHS DIST Z1 RCA
settings, and the reverse reach imped-
ance defined by
PHS DIST Z1 REV REACH
and
PHS DIST Z1 REV REACH RCA
as illustrated below.
MESSAGE
PHS DIST Z1
DIR COMP LIMIT: 90°
Range: 30 to 90° in steps of 1
MESSAGE
PHS DIST Z1 QUAD
RGT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
PHS DIST Z1 QUAD
LFT BLD: 10.00 ohms
Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
PHS DIST Z1 QUAD
LFT BLD RCA: 85°
Range: 60 to 90° in steps of 1
MESSAGE
PHS DIST Z1
SUPV: 0.200 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
PHS DIST Z1 VOLT
LEVEL: 0.000 pu
Range: 0.000 to 5.000 pu in steps of 0.001
MESSAGE
PHS DIST Z1
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
PHS DIST Z1 BLK:
Off
Range: FlexLogic™ operand
MESSAGE
PHS DIST Z1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHS DIST Z1
EVENTS: Disabled
Range: Disabled, Enabled
WARNING
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...