GE Multilin
L60 Line Phase Comparison System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
Continuous Monitor (Read/Write Setting)
6130
Continuous Monitor Function
0 to 1
---
1
F102
0 (Disabled)
6131
Continuous Monitor I OP
0 to 65535
---
1
F300
0
6132
Continuous Monitor I Supervision
0 to 65535
---
1
F300
0
6133
Continuous Monitor V OP
0 to 65535
---
1
F300
0
6134
Continuous Monitor V Supervision
0 to 65535
---
1
F300
0
6135
Continuous Monitor Target
0 to 2
---
1
F109
0 (Self-reset)
6136
Continuous Monitor Events
0 to 1
---
1
F102
0 (Disabled)
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)
6300
Negative Sequence Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
6301
Negative Sequence Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
6302
Negative Sequence Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
6303
Negative Sequence Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
6304
Negative Sequence Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
6305
Negative Sequence Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
6306
Negative Sequence Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
6307
Negative Sequence Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6308
Negative Sequence Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
6309
Reserved (7 items)
0 to 1
---
1
F001
0
6310
...Repeated for Negative Sequence Time Overcurrent 2
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
6400
Negative Sequence Instantaneous OC 1 Function
0 to 1
---
1
F102
0 (Disabled)
6401
Negative Sequence Instantaneous OC 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
6402
Negative Sequence Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
6403
Negative Sequence Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
6404
Negative Sequence Instantaneous OC 1 Reset Delay
0 to 600
s
0.01
F001
0
6405
Negative Sequence Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
6406
Negative Sequence Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6407
Negative Sequence Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
6408
Reserved (8 items)
0 to 1
---
1
F001
0
6410
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting)
64A0
Negative Sequence Overvoltage Function
0 to 1
---
1
F102
0 (Disabled)
64A1
Negative Sequence Overvoltage Source
0 to 5
---
1
F167
0 (SRC 1)
64A2
Negative Sequence Overvoltage Pickup
0 to 1.25
pu
0.001
F001
300
64A3
Negative Sequence Overvoltage Pickup Delay
0 to 600
s
0.01
F001
50
64A4
Negative Sequence Overvoltage Reset Delay
0 to 600
s
0.01
F001
50
64A5
Negative Sequence Overvoltage Block
0 to 65535
---
1
F300
0
64A6
Negative Sequence Overvoltage Target
0 to 2
---
1
F109
0 (Self-reset)
64A7
Negative Sequence Overvoltage Events
0 to 1
---
1
F102
0 (Disabled)
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
0 to 1
---
1
F102
0 (Disabled)
65C1
Power Swing Detect Source
0 to 5
---
1
F167
0 (SRC 1)
65C2
Power Swing Detect Mode
0 to 1
---
1
F513
0 (Two Step)
65C3
Power Swing Detect Supervision
0.05 to 30
pu
0.001
F001
600
65C4
Power Swing Detect Forward Reach
0.1 to 500
ohms
0.01
F001
5000
65C5
Power Swing Detect Forward RCA
40 to 90
degrees
1
F001
75
65C6
Power Swing Detect Reverse Reach
0.1 to 500
ohms
0.01
F001
5000
65C7
Power Swing Detect Reverse RCA
40 to 90
degrees
1
F001
75
65C8
Power Swing Detect Outer Limit Angle
40 to 140
degrees
1
F001
120
65C9
Power Swing Detect Middle Limit Angle
40 to 140
degrees
1
F001
90
65CA
Power Swing Detect Inner Limit Angle
40 to 140
degrees
1
F001
60
65CB
Power Swing Detect Delay 1 Pickup
0 to 65.535
s
0.001
F001
30
65CC
Power Swing Detect Delay 1 Reset
0 to 65.535
s
0.001
F001
50
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 55)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...