![background image](http://html.mh-extra.com/html/ge/ur-series/ur-series_instruction-manual_131898178.webp)
5-46
L60 Line Phase Comparison System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
USER-PROGRAMMABLE PUSHBUTTONS
Ö
USER PUSHBUTTON 1(16)
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
•
Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
•
Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic™ oper-
ands) into FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
USER PUSHBUTTON 1
PUSHBUTTON 1
FUNCTION: Disabled
Range: Self-Reset, Latched, Disabled
MESSAGE
PUSHBTN 1 ID TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 ON TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 OFF TEXT:
Range: Up to 20 alphanumeric characters
MESSAGE
PUSHBTN 1 HOLD:
0.0 s
Range: 0.0 to 10.0 s in steps of 0.1
MESSAGE
PUSHBTN 1 SET:
Off
Range: FlexLogic™ operand
MESSAGE
PUSHBTN 1 RESET:
Off
Range: FlexLogic™ operand
MESSAGE
PUSHBTN 1 AUTORST:
Disabled
Range: Disabled, Enabled
MESSAGE
PUSHBTN 1 AUTORST
DELAY: 1.0 s
Range: 0.2 to 600.0 s in steps of 0.1
MESSAGE
PUSHBTN 1 REMOTE:
Off
Range: FlexLogic™ operand
MESSAGE
PUSHBTN 1 LOCAL:
Off
Range: FlexLogic™ operand
MESSAGE
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
Range: 0 to 60.00 s in steps of 0.05
MESSAGE
PUSHBTN 1 LED CTL:
Off
Range: FlexLogic™ operand
MESSAGE
PUSHBTN 1 MESSAGE:
Disabled
Range: Disabled, Normal, High Priority
MESSAGE
PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...