GE Multilin
L60 Line Phase Comparison System
5-125
5 SETTINGS
5.5 GROUPED ELEMENTS
5
5.5.4 LINE PICKUP
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
LINE PICKUP
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately, the user may assign a FlexLogic™ operand to the
TERMINAL OPEN
setting that specifies the ter-
minal status. Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been
closed onto a fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high speed automatic reclosure (AR) is
employed. The
AR CO-ORD DELAY
setting allows the overcurrent setting to be below the expected load current seen after
reclose. Co-ordination is achieved by all of the
LINE PICKP UV
elements resetting and blocking the trip path before the
AR
CO-ORD DELAY
times out. The
AR CO-ORD BYPASS
setting is normally enabled. It is disabled if high speed autoreclosure is
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local ter-
minal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues
a close command results in the
LINE PICKUP RCL TRIP
FlexLogic™ operand. For security, the overcurrent trip is supervised
LINE PICKUP
LINE PICKUP
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LINE PICKUP SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
PHASE IOC LINE
PICKUP: 1.000 pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
LINE PICKUP UV PKP:
0.700 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
LINE END OPEN PICKUP
DELAY: 0.150
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LINE END OPEN RESET
DELAY: 0.090
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
LINE PICKUP OV PKP
DELAY: 0.040
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
AR CO-ORD BYPASS:
Enabled
Range: Disabled, Enabled
MESSAGE
AR CO-ORD PICKUP
DELAY: 0.045
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
AR CO-ORD RESET
DELAY: 0.005
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TERMINAL OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
AR ACCELERATE:
Off
Range: FlexLogic™ operand
MESSAGE
LINE PICKUP DISTANCE
TRIP: Enabled
Range: Disabled, Enabled
MESSAGE
LINE PICKUP BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
LINE PICKUP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LINE PICKUP
EVENTS: Disabled
Range: Disabled, Enabled
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...