5-112
L60 Line Phase Comparison System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
Refer to chapter 9:
Application of settings
for the calculation examples for the phase comparison element.
In single phase comparison schemes, coincidence of the local and remote squares is detected during half the power cycle
only, positive or negative. As a result, some delay in operation can be expected under
unfavorable
fault inception. This
weakness of the single phase comparison schemes is eliminated in dual phase comparison schemes but cost of the com-
munication link is higher.
Table 5–13: 87PC OSCILLOGRAPHY CHANNELS
CFG FILE LABEL
DESCRIPTION
X1: IA
Phase A of the F module CT bank
X2: IB
Phase B of the F module CT bank
X3: IC
Phase C of the F module CT bank
X#: IA
Phase A of the X module CT bank
X#: IB
Phase B of the X module CT bank
X#: IC
Phase C of the X module CT bank
87PC BKR1 Current
Effective mixed operating signal of BKR1
87PC BKR1 POS
Positive current pulse for the first breaker
87PC BKR1 NEG
Negative current pulse for the first breaker
87PC BKR1 Mag
Magnitude of the effective operating signal of BKR1
87PC BKR1 FDL
Low-set fault detection for the first breaker
87PC BKR1 FDH
High-set fault detection for the first breaker
87PC BKR2 Current
Effective mixed operating signal of BKK2
87PC BKR2 POS
Positive current pulse for the second breaker
87PC BKR2 NEG
Negative current pulse for the second breaker
87PC BKR2 Mag
Magnitude of the effective operating signal of BKR2
87PC BKR2 FDL
Low-set fault detection for the second breaker
87PC BKR2 FDH
High-set fault detection for the second breaker
87PC POS
Positive current local pulse for both breakers
87PC NEG
Negative current local pulse for both breakers
87PC FDL
Low-set fault detection for both breakers
87PC FDH
High-set fault detection for both breakers
87PC Rx1P Voltage
Received pulse (voltage) on channel 1P
87PC Rx1P
Received pulse on channel 1P
87PC Rx1N Voltage
Received (voltage) on channel 1N
87PC Rx1N
Received pulse on channel 1N
87PC Rx2P Voltage
Received pulse (voltage) on channel 2P
87PC Rx2P
Received pulse on channel 2P
87PC Rx2N Voltage
Received pulse (voltage) on channel 2N
87PC Rx2N
Received pulse on channel 2N
87PC POS Aligned
Aligned (delayed) local positive pulse
87PC NEG Aligned
Aligned (delayed) local negative pulse
87PC Rx1P Aligned
Received and conditioned pulse on channel 1P
87PC Rx1N Aligned
Received and conditioned pulse on channel 1N
87PC Rx2P Aligned
Received and conditioned pulse on channel 2P
87PC Rx2N Aligned
Received and conditioned pulse on channel 2N
87PC POS Int Input
Input of the positive integrator
87PC NEG Int Input
Input of the negative integrator
87PC POS Integrator
Positive integrator in (degrees)
87PC NEG Integrator
Negative integrator in (degrees)
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...