2-16
L60 Line Phase Comparison System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.2.6 POWER SUPPLY
LOW RANGE
Nominal DC voltage:
24 to 48 V
Min/max DC voltage:
20 / 60 V
Voltage loss hold-up:
20 ms duration at nominal
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
125 to 250 V
Min/max DC voltage:
88 / 300 V
Nominal AC voltage:
100 to 240 V at 50/60 Hz
Min/max AC voltage:
88 / 265 V at 25 to 100 Hz
Voltage loss hold-up:
200 ms duration at nominal
ALL RANGES
Volt withstand:
2
×
Highest Nominal Voltage for 10 ms
Power consumption:
typical = 15 to 20 W/VA
maximum = 50 W/VA
contact factory for exact order code con-
sumption
INTERNAL FUSE
RATINGS
Low range power supply: 8 A / 250 V
High range power supply: 4 A / 250 V
INTERRUPTING CAPACITY
AC:
100 000 A RMS symmetrical
DC:
10 000 A
2.2.7 OUTPUTS
FORM-A RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 4 ms
Contact material:
silver alloy
LATCHING RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
6 A
Break at L/R of 40 ms:
0.25 A DC max.
Operate time:
< 4 ms
Contact material:
silver alloy
Control:
separate operate and reset inputs
Control mode:
operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR
Applicable voltage:
approx. 15 to 250 V DC
Trickle current:
approx. 1 to 2.5 mA
FORM-A CURRENT MONITOR
Threshold current:
approx. 80 to 100 mA
FORM-C AND CRITICAL FAILURE RELAY
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Carry continuous:
8 A
Break (DC inductive, L/R = 40 ms):
Operate time:
< 8 ms
Contact material:
silver alloy
FAST FORM-C RELAY
Make and carry:
0.1 A max. (resistive load)
Minimum load impedance:
Operate time:
< 0.6 ms
Internal Limiting Resistor: 100
Ω
, 2 W
SOLID-STATE OUTPUT RELAY
Operate and release time: <100
μ
s
Maximum voltage:
265 V DC
Maximum continuous current: 5 A at 45°C; 4 A at 65°C
Make and carry:
for 0.2 s:
30 A as per ANSI C37.90
for 0.03 s
300 A
Breaking capacity:
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
VOLTAGE
CURRENT
24 V
1 A
48 V
0.5 A
125 V
0.3 A
250 V
0.2 A
INPUT
VOLTAGE
IMPEDANCE
2 W RESISTOR
1 W RESISTOR
250 V DC
20 K
Ω
50 K
Ω
120 V DC
5 K
Ω
2 K
Ω
48 V DC
2 K
Ω
2 K
Ω
24 V DC
2 K
Ω
2 K
Ω
Note: values for 24 V and 48 V are the same due to a
required 95% voltage drop across the load impedance.
UL508
Utility
application
(autoreclose
scheme)
Industrial
application
Operations/
interval
5000 ops /
1 s-On, 9 s-Off
5 ops /
0.2 s-On,
0.2 s-Off
within 1
minute
10000 ops /
0.2 s-On,
30 s-Off
1000 ops /
0.5 s-On, 0.5 s-Off
Break
capability
(0 to 250 V
DC)
3.2 A
L/R = 10 ms
10 A
L/R = 40 ms
10 A
L/R = 40 ms
1.6 A
L/R = 20 ms
0.8 A
L/R = 40 ms
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...