2.1.10
UCSC Hardware Replacement
Replacement parts may contain static-sensitive components. Therefore, GE ships replacement parts in anti-static bags. When
handling electronics, make sure to store them in anti-static bags or boxes and use a grounding strap.
Caution
To prevent component damage caused by static electricity, treat all boards with
static-sensitive handling techniques. Wear a wrist grounding strap when handling
boards or components, but only after boards or components have been removed from
potentially energized equipment and are at a normally grounded workstation.
Warning
In addition to information provided here, always follow all wiring and safety codes
that apply to your area or your type of equipment. For example, in the United States,
most areas have adopted the National Electrical Code standard and specify that all
wiring conform to its requirements. In other countries, different codes will apply. For
maximum safety to personnel and property you must follow these codes. Failure to do
so can lead to personal injury or death, property damage or destruction, or both.
➢
➢
To replace the UCSC with another UCSC
1.
Loosen the screws holding the power connector in place.
2.
Disconnect the power connector from the controller.
3.
Disconnect all Ethernet cables (note which cable is connected to which port).
4.
Loosen the screws holding the controller in place. The mounting is a keyhole design.
5.
Remove the controller by lifting to align the large portion of the keyhole with the mounting screws and pull forward.
6.
Verify that the hardware revision of the old UCSC is the same or compatible with the new UCSC for its particular
application.
7.
Reinstall the new controller by reversing steps 2 through 4. Do not apply power yet.
8.
Perform the UCSC Restore procedure to initialize the new controller.
9.
If restore was not successful, configure the new controller’s UDH network address.
10.
Use the ToolboxST application to Build and Download to the controller as needed. Refer to the
ToolboxST User Guide
for Mark VIeS Functional Safety Systems
(GEH-6862), the section
Download to Controller
for instructions.
Controllers
GEH-6855_Vol_II System Guide 35
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...