143-154
Description
Relay Output Coil [ ] does not match commanded state
Possible Cause
•
The relay feedback does not match the commanded state for TRLY__B, TRLY__F, or SRLY, or SRSA specific terminal
boards.
•
SRSA: The mechanical relay (1 or 7) is not picked up when the relay (2-6 or 8-12) is closed.
•
SRSA: Wetting power A (relays 2-6) or B (relays 8-12) is not applied.
•
SRSA: Relay is picked up but no current (minimum 100 mA) is flowing through the relay circuit.
Solution
•
Clear the voter disagreements.
•
Check the I/O pack connector alignment and seating.
•
Check the I/O pack configuration.
•
SRSA: Pick up the mechanical relay before closing the solid state relays.
•
SRSA: Verify that the wetting power bank A and B have voltage applied.
•
SRSA: Verify that a proper output circuit is connected to the relay.
•
Replace the terminal board.
155-166
Description
NO [Normally Open] contact [ ] voltage disagreement with command
Possible Cause
Voltage is not detected across an open TRLY__C or TRLY__E output contact.
Solution
•
Clear the voter disagreements.
•
Check the application to ensure that voltage should be present when relay is open.
•
Check that the voltage is within the published detection range. Refer to the terminal board help documentation.
•
Check the I/O pack configuration.
•
Replace the terminal board.
167-178
Description
Relay Driver [ ] does not match commanded state
Possible Cause
The relay command signal, displayed at the I/O pack output connector to the terminal board, does not
match the commanded state.
Solution
The command signal feedback requires a properly connected terminal board.
•
Check the I/O pack to terminal board connector alignment and seating.
•
Replace the I/O pack.
•
Replace the terminal board.
140
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...