7.8
RTD Inputs
The YUAA has an RTD input performance equivalent to the existing SRTD for RSS accuracy covering 100 to 200 ohm
sensors, with slow speed only (no fast mode). Analog channels support RTD inputs covering resistance spans matching
Nickel and Platinum sensors, as compared to the existing SRTD. Resistance input from RTD sensors can be from 60 to 450
ohms, using 3–wire connections, with or without a shared return line.
RTD (3–wire) processing uses a single channel, with the channel alternating between voltage and current measurements to
derive the sensed resistance. The currents are provided by the dual current sources, while the DAC terminal on the SUAA is
an active ground to return the current. The YUAA does not support Fast mode. A single Slow mode of operation is used, with
an acquisition time of 500 milliseconds or faster for 16 channels.
RTD
Sensor
( 3 wire )
I / O+
I / O-
RTN
RTD
Sensor
( 3 wire )
I / O+
I / O-
RTN
RTD
Sensor
( 3 wire )
I / O+
I / O-
RTN
RTD
Sensor
( 3 wire )
I / O+
I / O-
Shared Return
to one channel
Individual Returns
to each channel
RTD Wiring
The I/O pack configuration and the final ohms value is used to lookup a temperature value based on the type of RTD selected.
This final value is returned in signal space as either ohms or a temperature in degrees (Celsius or Fahrenheit set by parameter
). The available RTD types are displayed in the following table, using a current source of up to 1 mA with a
compliance voltage range of up to 5 V.
RTD Types and Temperature Ranges
Value
RTD Type
Compatible Device Types
Min Temp (ºF)
Max Temp (ºF)
1
Minco PD
PT100 DIN
-325.893
1566.553
2
Minco PA
PT100 PURE
-323.885
1167.418
3
Minco PB
PT100 USIND
-329.068
1166.875
Rosemount 104
4
Minco NA
N 120
-113.662
499.599
5
Minco PIA
None
-413.319
1765.473
6
Minco SAMA
SAMA 100
-322.438
1112.704
7
Minco PK
PT 200
-101.918
511.573
8
Minco PN
None
-101.918
511.573
10
Minco CA
CU10
-153.768
531.560
9
Ohms
Not Applicable
< 10 ohms
625 ohms
YUAA Universal I/O Modules
GEH-6855_Vol_II System Guide 191
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...