When the Redundancy OK floating signal contact opens, it indicates the loss of redundancy. Loss of redundancy may be a
result of the following issues:
•
The decoupled component is defective.
•
At least one input voltage is too low or does not exist.
•
If the load current is higher than the set threshold value of I
N
, a single power supply unit can no longer sustain the load
(indicated after 4 sec).
When the ACB OK floating signal contact opens, it indicates that the load current is not distributed symmetrically on both
parallel connected power supply units.
ABC OK Signal Output Operation
Redundancy OK Signal Output Operation
10.10.3.7
Power Supply Redundant Operation
Redundant power supplies are recommended for use in systems with especially high requirements for operational safety. With
redundant power supplies, if a fault occurs in the Primary circuit of the first power supply, the second device automatically
takes over supplying power, without interruption, and vice versa. For this purpose, the power supply units to be connected in
parallel are dimensioned so that the total current requirement of all consumers is completely covered by one power supply
unit. However, 100% redundancy makes external decoupling diodes (GE Part Number 342A3648PD40A48) necessary.
Redundant Parallel Connection
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 417
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...