2624-2655
Description
IOPoint [ ] - HART extended status mismatch - configured: [ ] received: [ ]
Possible Cause
The number of extended status bytes returned in Hart Message 48 (Read extended status) does not agree
with the ToolboxST configuration.
Solution
Verify that the correct device is attached, and set the ToolboxST configured value to either 0 or the received
value.
2656
Description
HART control messages disabled. AMS HART messages only
Possible Cause
The
AMS_Msgs_Only
parameter is
Enabled
. No control messages are sent. This parameter overrides
the values in the
Hart_Ctrl
and
Hart_ExStatus
for each individual channel.
Solution
•
To send AMS messages only, but clear this alarm: Set the
AMS_Msgs_Only
parameter to
Disabled
and set each
channel's
Hart_Ctrl
and
Hart_ExStatus
to zero.
•
To allow control messages
and
AMS messages, set
AMS_Msgs_Only
to
Disabled
.
2657
Description
Coldjunction temperature [ ] value beyond specified table limits (-40 to 102°C, -40 to 215 °F)
Possible Cause
•
Cold Junction temperature exceeds the lookup table range (-40 to 101.67°C) or (-40 to 215 °F)
•
Ambient temperature is too hot/cold
Solution
•
If remote or backup cold junction is being used, then confirm those values are within the lookup table range.
•
Check the ambient temperature. If the temperatures are too high or low, power off the I/O pack and restart it after the
ambient temperatures are within (-40 to 101.67°C) or (-40 to 215 °F).
2658-2689
Description
IOPoint [ ] - Internal burden resistor protection activated
Possible Cause
•
The I/O pack has detected too much ( > 30 mA) current flowing through the internal burden resistor on indicated I/O
point and has opened an internal switch to protect the given I/O point. The I/O pack periodically closes the switch and
checks again if the current has dropped below the threshold.
•
Improper device operation or Improper wiring
Solution
•
Check the field wiring and determine if a connected device is sourcing currents beyond the specified range on the given
I/O point.
•
After checking and correcting the wiring, wait approximately 15 seconds for the error to correct itself.
222
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...