Description
JPDG DC 24V Voltage GND fdbk mag (JPS1/JPS2 connector) out of range
Possible Cause
•
The 24/48 V dc ground feedback magnitude is greater than the Gnd_Mag_Trig_Volt.
•
The Gnd_Mag_Trig_Volt is set too low.
•
Only one side of the 24/48 V dc source voltage is grounded.
Solution
•
Verify that the Gnd_Mag_Trig_Volt is set correctly.
•
Check the connections to the specified connector.
•
Check the grounding of the dc input signals.
•
If 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to
Disabled
.
210 – 211
Description
JPDG DC 24V Voltage dry contact input [ ] (P4 connector) not OK
Possible Cause
•
The power supply contact is open. The power supply is not operating normally.
•
The power supply dry contact feedback is not connected to the terminal board P4 connector.
Solution
•
Verify the status of the power supply contact, and that the power supply is operating correctly.
•
Check the connections between the power supply and the P4 connector on the JPDG.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to
Disabled
.
212
Description
JPDG fuse FU10/FU11 (JFA connector) is blown
Possible Cause
The FU10 or FU11 fuse is blown.
Solution
•
Replace the fuse.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to
Disabled
.
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 359
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...