153, 161
Description
JPDE-[ ] fuse FU21/FU22 (JS2 connector) is blown or SWS2 switched OFF.
Possible Cause
•
The SWS2 is turned off and
FuseDiag
is enabled.
•
The FU21 or FU22 fuse is blown.
•
The 24/48 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting
FuseDiag
to
Disable.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 24/48 V dc input connections to the terminal board.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_24VFdbkMag
) to
Disabled
.
154, 162
Description
JPDE-[ ] fuse FU31/FU32 (JS3 connector) is blown or SWS3 switched OFF.
Possible Cause
•
The SWS3 is turned off and
FuseDiag
is enabled.
•
The FU31 or FU32 fuse is blown.
•
The 24/48 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting
FuseDiag
to
Disable.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 24/48 V dc input connections to the terminal board.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_24VFdbkMag
) to
Disabled
.
342
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...