7.12.3
Voltage Inputs
Voltage Inputs
InputType
Low_Input
Low_Value
High_Input
High_Value
InputFilter
Description
Type of
Analog Input
Input Volts at
Low Value
Low Input in
Engineering Units
Input Volts at
High Value
High Input in
Engineering
Units
Filter
Bandwidth in
Hz
Choices
{defaults}
+/-10volt
{+/-5volt}
{-5}
{0}
{5}
{100}
0.75, 1.5, 3, 6,
12, {Unused}
Low_Input, Low_Value, High_Input, High_Value settings are used by the I/O pack firmware to define the linear relationship
between Volts and customer-defined engineering units. The I/O Point value will be in Engineering units. Engineering units are
specific to the field device being used.
7.12.4
RTDs
RTDType
Compatible Type
Notes
MINCO_NA
N 120
RTDType selects the type of RTD device connected to the input. The Ohms type returns a
value of resistance, with the TempUnits parameter ignored.
The temperature units parameter, TempUnits, can be either Fahrenheit or Celsius, and is
set from the Parameters tab.
MINCO_PA
PT100 PURE
MINCO_PB
PT100 USIND
{MINCO_PD}
PT100 DIN
MINCO_PIA
MINCO_PK
PT 200
MINCO_PN
MINCO_CA
CU10
Ohms
PT100_SAMA
SAMA 100
7.12.5
Thermocouples
ThermCplType
ReportOpenTC
Notes
B
E
J
K
{mV}
N
R
S
T
{Fail_Cold}
Fail_Hot
ThermCplType selects the type of TC device connected to the input. The mV type shall
only return a value of millivolts, the Units parameter shall be ignored for this type, and no
cold junction compensation shall be performed.
ReportOpenTC is a Fail_Hot/Fail_Cold configuration to control the reported TC value when
an open circuit occurs. On open circuit detection the I/O pack will report the calculated
value at -40 mV (Open TC Threshold) when Fail_Cold in enabled, and will report 3632 ºF
(2000 ºC) when Fail_Hot is enabled.
The temperature units parameter, TempUnits, can be either Fahrenheit or Celsius, and is
set from the Parameters tab.
YUAA Universal I/O Modules
GEH-6855_Vol_II System Guide 205
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...